Engineering and remote access
3.8 OPC UA server
Display name
DeviceMaxCurrent
DeviceOutputCurrent
DeviceOutputVoltage
DeviceP1LinkLed
DeviceP2LinkLed
DeviceRunLed
DeviceSFLed
DeviceSWSettings
Valid
DeviceStateLed
DeviceTemperature
DeviceTotalOperating
Time
3.8.6.6

ActualUpdateState

Display name
UpdateProgress
UpdateState
3.8.6.7

Alarm

Display name
AlarmBattery
ConnectionBroken
AlarmBattery
ConnectionHigh
Resistive
AlarmBatteryDeep
Discharge
AlarmBatteryDeep
DischargeNoCharging
Possible
AlarmBatteryDefekt
AlarmBatterySOHTest
170
Data type
Definition
Float
AnalogItemType Maximum output current supported by the SITOP UPS1600
Float
AnalogItemType Measured output current of SITOP UPS1600
Float
AnalogItemType Maximum output voltage
Object
Sitop_1600_
LedType
Object
Sitop_1600_
LedType
Object
Sitop_1600_
LedType
Object
Sitop_1600_
LedType
Boolean
PropertyType
Object
Sitop_1600_
LedType
Sbyte
AnalogItemType Device temperature
UInt32
AnalogItemType Battery-specific data: Total time for which battery was in
Data type
Definition
Integer
PropertyType
Enumeration
MultiState
DiscreteType
Data type
Definition
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Description
Status of LED "P1"
Status of LED "P2"
Status of LED "RUN"
Status of LED "SF"
This object provides information about whether the SW
parameters or the parameters at the rotary switches are
used. The desired setting is selected on rotating switch for
threshold voltage.
Status of LED "OK": Device status
buffer mode during its service life
Description
Update progress
Update status
Description
Connection to battery interrupted - check connection and
fuse
High-resistance connection to battery - check battery power
cable
Battery is deep discharged - no buffering possible
Battery is deep discharged - replace battery
Battery defective - check fuse and battery voltages
Battery 'state of health' (SOH) tests are in progress