Actualupdatestate; Alarm - Siemens SITOP UPS1600 Equipment Manual

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Engineering and remote access
3.10 OPC UA server
Display name
Data type
DeviceInputCurrent
Float
DeviceInputVoltage
Float
DeviceInputVoltageOK
Boolean
DeviceLoadCurrent
Float
DeviceMaxCurrent
Float
DeviceOutputCurrent
Float
DeviceOutputVoltage
Float
DeviceP1LinkLed
Object
DeviceP2LinkLed
Object
DeviceRunLed
Object
DeviceSFLed
Object
DeviceSWSettings
Boolean
Valid
DeviceStateLed
Object
DeviceTemperature
Sbyte
DeviceTotalOperating
UInt32
Time
3.10.6.6

ActualUpdateState

Display name
Data type
UpdateProgress
Integer
UpdateState
Enumeration
3.10.6.7

Alarm

Display name
Data type
AlarmBattery
Boolean
ConnectionBroken
AlarmBattery
Boolean
ConnectionHigh
Resistive
AlarmBatteryDeep
Boolean
Discharge
AlarmBatteryDeep
Boolean
DischargeNoCharging
Possible
AlarmBatteryDefect
Boolean
168
Definition
Description
AnalogItemType
Measured input current of SITOP UPS1600
AnalogItemType
Input voltage
PropertyType
Input voltage has exceeded the configured threshold volt-
age. Connected devices are powered with the input supply.
AnalogItemType
Measured output current of SITOP UPS1600
AnalogItemType
Maximum output current supported by the SITOP UPS1600
AnalogItemType
Measured output current of SITOP UPS1600
AnalogItemType
Measured output voltage
Sitop_1600_
Status of LED "P1"
LedType
Sitop_1600_
Status of LED "P2"
LedType
Sitop_1600_
Status of LED "RUN"
LedType
Sitop_1600_
Status of LED "SF"
LedType
PropertyType
This object provides information about whether the SW
parameters or the parameters at the rotary switches are
used. The corresponding setting should be made at the rota-
ry coding switch for the buffer threshold.
Sitop_1600_
Status of LED "OK" Device status
LedType
AnalogItemType
Device temperature
AnalogItemType
Battery-specific data: Total time for which battery was in
buffer mode during its service life
Definition
Description
PropertyType
Update progress
MultiState
Update status
DiscreteType
Definition
Description
PropertyType
Connection to battery interrupted - check connection and
fuse
PropertyType
High-resistance connection to battery - check battery power
cable
PropertyType
Battery is deep discharged - no buffering possible.
PropertyType
Battery is deep discharged - replace battery.
PropertyType
Battery defective - check fuse and battery voltages.
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76