Sitop Bat1600 - Siemens SITOP UPS1600 Equipment Manual

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

8.2.2

SITOP BAT1600

Battery modules
6EP4132-0JA00-
0AY0
(2.5 Ah)
Rated output voltage
24 V DC
U
out rated
Output voltage range 28.8 - 20.5 V
Rated output current
10 A
I
out rated
Capacity
2.5 Ah
Battery modules that
max. 6
can be connected in
parallel
Power boost for
30 A
30 ms
Extra power for
15 A
5 s/min
Fuse
Flat fuse 25 A, 32 V DC, 1000 A (IR),
MAXI (Littelfuse 576-0299025.ZXNV)
Remark:
The lead acid batteries are fully charged when the device is delivered. The LiFePO4 battery
(2.5 Ah and 7.5 Ah) is only supplied, charged up to a maximum of 30 % of the rated charge
(to comply with transport regulations).
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
6EP4133-0GA00-
6EP4134-0JA00-
0AY0
0AY0
(3.2 Ah)
(7.5 Ah)
27.3 - 20.0 V
28.8 - 20.5 V
20 A
40 A
3.2 Ah
7.5 Ah
60 A
120 A
30 A
60 A
Flat fuse 50 A, 32 V DC, 1000 A (IR), MAXI (Littelfuse 576-
0299050.ZXNV)
Technical data
8.2 Output data
6EP4135-0GE00-
6EP4137-
0AY0
0GE00-0AY0
(12 Ah)
(38 Ah)
27.3 - 20.0 V
27.3 - 20.0 V
40 A
40 A
12 Ah
38 Ah
120 A
120 A
60 A
60 A
239