Siemens SITOP UPS1600 Equipment Manual page 176

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Engineering and remote access
3.10 OPC UA server
ActualState
Display name
Data type
BatteryCalculated
Byte
Health
BatteryOperatingState
Byte
ModuleCapacity
Float
ModuleChange
Boolean
Recommended
ModuleCompound
Enumeration
ModuleConnection
Boolean
Fault
ModuleManufactoring
Date
Date
ModuleMax
Sbyte
Temperature
ModuleMin
Sbyte
Temperature
ModuleStandbyTime
UInt32
ModuleStateLed
Object
ModuleTemperature
Sbyte
Alarm
Display name
Data type
AlarmBatteryChange
Boolean
Canceled
AlarmBatteryChange
Boolean
Finished
AlarmBatteryChange
Boolean
Started
AlarmBattery
Boolean
CommunicationFault
AlarmBatteryDeepDis-
Boolean
chargedNoCharging
Possible
AlarmBatteryDefect
Boolean
AlarmBatteryEndOf
Boolean
LifetimePrewarning
AlarmBattery
Boolean
EndOfLifetimeWarning
AlarmBattery
Boolean
TemperatureHigh
AlarmBattery
Boolean
TemperatureLow
AlarmFuseBroken
Boolean
AlarmIncompatible
Boolean
ModuleDetected
176
Definition
Description
AnalogItemType
Calculated battery state (only for SITOP BAT1600)
AnalogItemType
Battery status (only for SITOP BAT1600)
AnalogItemType
Battery capacity: Total battery capacity of all energy storage
devices connected to the SITOP UPS1600.
PropertyType
Battery capacity is insufficient to achieve the specified buffer
time.
MultiState
Connected device
DiscreteType
PropertyType
Connection to battery interrupted - check connection and
fuse
PropertyType
Manufacturing date
AnalogItemType
Maximum specified operating temperature of the battery.
AnalogItemType
Minimum specified operating temperature of the battery.
AnalogItemType
Battery-specific data: Time for which battery was connected
but no power was consumed.
Sitop_1600_
ModuleStateLed
LedType
AnalogItemType
Battery temperature
Definition
Description
PropertyType
Battery replacement canceled - battery parameters are not
reset.
PropertyType
Battery replacement finished - counters have been reset.
PropertyType
Battery replacement started by user
PropertyType
Communication with formerly known battery is no longer
possible - check communication
PropertyType
Battery is deep discharged, charging not possible.
PropertyType
Battery defective - check fuse and battery voltages.
PropertyType
Calculated battery service life almost reached. Only restrict-
ed buffer readiness probable.
PropertyType
Calculated battery service life reached, battery replacement
recommended.
PropertyType
Battery temperature too high - battery life will be shortened
PropertyType
Battery temperature too low - reduced output current
PropertyType
Fuse is defective.
PropertyType
Incompatible battery module detected.
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76