Siemens SITOP UPS1600 Equipment Manual page 122

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Engineering and remote access
3.6 Cyclic and acyclic data
Data
LED state
Fill byte(s)
SWD
Battery MID
0x0020: State information (reading)
Data
Remaining buffer time [1 s]
Total operating time [1 h]
Total calculated battery capacity
[0.1 Ah]
Calculated battery 1 capacity
[0.1 Ah]
Calculated battery 2 capacity
[0.1 Ah]
Calculated battery 3 capacity
[0.1 Ah]
Calculated battery 4 capacity
[0.1 Ah]
Calculated battery 5 capacity
[0.1 Ah]
Calculated battery 6 capacity
[0.1 Ah]
Input voltage [0.01 V]
Input current [5 mA]
Output voltage [0.01 V]
Load current [5 mA]
Measured charge current [1 mA]
Battery voltage [0.01 V]
Output current [5 mA]
Charge voltage [0.01 V]
Fill byte(s)
Valid configuration
Number of batteries
Fill byte(s)
Battery 1 change recommended
Battery 2 change recommended
122
Description
LED states
-
SW revision
Battery Module Ident Number
Description
Probable remaining buffer time. The remaining buffer time is cal-
culated based on the present battery charge and the average cur-
rent over a 10 minute period.
Total operating time.
Total calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Battery 1: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Battery 2: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Battery 3: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Battery 4: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Battery 5: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Battery 6: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Input voltage: Measured rms value of the supply voltage at the
input of the SITOP UPS1600.
Current measured at the input of the SITOP UPS1600.
Voltage measured at the output of the SITOP UPS1600.
Load current measured at the output of the SITOP UPS1600.
Measured battery charge current of the SITOP UPS1600.
Measured battery voltage of the connected battery modules
Load current measured at the output of the SITOP UPS1600.
Voltage used to charge the battery during the constant-current
charging phase
-
Valid configuration: Indicates whether the software parameters or
the parameters at the rotary coding switch are used. The corre-
sponding setting should be made at the rotary coding switch for
the buffer threshold.
Number of connected battery modules. Here, only SITOP BAT1600
or SITOP UPS1100 battery modules (SITOP system batteries) are
counted.
-
Battery 1: Battery replacement recommended: The battery capacity
is not sufficient for the defined buffer time.
Battery 2: Battery replacement recommended: The battery capacity
is not sufficient for the defined buffer time.
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
Data type
Unsigned8
2 x Unsigned8
Unsigned32
Unsigned32
Data type
Unsigned32
Unsigned32
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
3 x Unsigned8
Unsigned8
Unsigned8
7 x Unsigned8
Unsigned8
Unsigned8