Mounting/removing

5.1

SITOP UPS1600

Installing the device in a housing or a control cabinet
The SITOP UPS1600s are built-in units. They must be installed in a housing or control
cabinet where only qualified personnel have access.
The device can be mounted in a control cabinet on DIN rails (see Chapter Mechanical system
(Page 246))
Use in hazardous zones
If the device is to be used in a hazardous zone (II 3G Ex nA nC IIC T4 Gc) it must be installed
in a distribution box with degree of protection IP54 or higher. This distribution box must
comply with the requirements of EN 60079-15.
Mounting
To mount the device, position it with the DIN rail guide at the upper edge of the standard
mounting rail and press down to lock it into place. If this is too difficult, press slider ⑩ at the
same time, as described under "Removal".
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76