You can find detailed information about the individual data sets in Section Data sets
(Page 109)
3.6.2.1

Data sets

In this section you can find detailed information about the individual data sets that are sent
from the PROFINET IO-Controller to the SITOP UPS1600 - and which can be read from the
SITOP UPS1600.
0x0001: Buffering parameters (reading/writing)
Data
Buffer time [1 s]
Buffer time 2 [1 s]
Buffer threshold [0.01 V]
Stop buffering voltage [0.01 V]
Input voltage OK time [1 ms]
Downtime alarm [1 ms]
Buffering allowed
Enable reset after buffering
Discharge cut-off voltage
0x0004: Reset parameters (reading/writing)
Data
Reset time [1 s]
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
Data set
Type
NTP client status pa-
Reading
rameters
PROFINETSecurity
Reading/
writing
Description
Buffer time: After the selected buffer time has expired, the SITOP
UPS1600 switches off the load output. The actual buffer time that
can be achieved depends on the connected loads and energy stor-
age devices.
Additional buffer time after the PC was shut down. (only valid in
conjunction with PC software SITOP Manager)
Connection threshold: Switching voltage for buffering. Buffering is
active below this value.
Buffer mode is exited if the battery voltage is below this value.
Wait time for stable input voltage: Minimum time during which the
input voltage during buffer mode must be available at the SITOP
UPS1600 to exit buffer mode of the SITOP UPS1600 and to again
supply the connected loads via the input voltage (normal opera-
tion).
Downtime alarm: Alarm filter: An alarm is only sent if it is active for
longer than the set time.
Activate or deactivate buffer mode. This setting is only accepted by
the SITOP UPS1600 in the Remote Enable (REN) operating mode.
Enable reset after buffering: If, during buffer mode, the input volt-
age becomes available again, then the output is switched off for a
selectable time in order to reset the connected devices.
The discharge cut-off voltage is a voltage to be set, which must not
be fallen below in the case of a buffering event.
Description
Reset time: Time during which the SITOP UPS1600 output is shut
down if the connected devices are reset.
Engineering and remote access
Description
Status NTP client
Setting for DCP write protection
3.6 Cyclic and acyclic data
Data size
40 bytes
(from V2.2)
2 bytes
(from V2.2)
Data type
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned8
Unsigned8
Unsigned16
Data type
Unsigned8
109