Engineering and remote access
3.5 SIMATIC STEP 7
3. In the "Select node address" dialog, if necessary, click the "Display" button to display the
actual accessible modules (these include the IO controller to be loaded with its current IP
address or its MAC address, if no IP address is yet available).
4. Select the IO controller to be loaded from the accessible modules.
This module is displayed in the "Enter connection to target station" dialog box.
5. Start loading by clicking on the "OK" button.
The IO controller is assigned the configured IP address.
Note
Ensure that the article number of the SITOP UPS1600 configured offline matches the article
number of the device connected online.
The following response is obtained after loading the configuration into the device:
Figure 3-2
100
Online / offline
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76