Battery; Buffering - Siemens SITOP UPS1600 Equipment Manual

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Engineering and remote access
3.10 OPC UA server
Display name
Data type
AlarmLow
Boolean
VoltageMode
AlarmNoCharging
Boolean
ManualDeactivated
AlarmOutputTurnedOff Boolean
AlarmOutputTurnedOn Boolean
AlarmOverCurrent
Boolean
AlarmResetExecuted
Boolean
AlarmSurplusBattery
Boolean
AlarmUnknownBattery Boolean
AlarmWrongBattery
Boolean
Polarity
3.10.6.8

Battery

Display name
Data type
BatteryCapacity
Float
Setpoint
BatteryDefectVoltage
Float
Setpoint
BatteryIgnoreCoding
Boolean
Setpoint
BatteryInspection
Byte
TimeSetpoint
3.10.6.9

Buffering

Display name
Data type
BufferExpected
Float
CurrentSetpoint
BufferThreshold
Float
Setpoint
BufferTime2Setpoint
UInt16
BufferTimeSetpoint
UInt16
BufferingEnableSet-
Boolean
point
170
Definition
Description
PropertyType
Input voltage of SITOP UPS1600 is too low. The buffer of the
SITOP UPS1600 is not operational.
PropertyType
Charging function was deactivated by a control command
PropertyType
Output of SITOP UPS1600 has been switched off due to the
execution of a command or because an error situation has
occurred (e.g. temperature or output current too high).
PropertyType
Output of SITOP UPS1600 has been switched on again due
to the execution of a command or because an error situation
has been remedied.
PropertyType
Output current of SITOP UPS1600 is too high. Output is
switched off for 20 s. The output is switched on again after
20 s.
PropertyType
Input voltage connected to SITOP UPS1600 was already OK
before the buffer time expired. Connected devices are reset
by switching off the SITOP UPS1600 outputs for the parame-
terized time.
PropertyType
More than 6 batteries are connected. Connect max. of
6 batteries to the Energy Storage Link.
PropertyType
Data from the battery cannot be read correctly. Battery is
defective or not supported by SIEMENS.
PropertyType
Wrong battery polarity - check battery connections.
Definition
Description
AnalogItemType
Total battery capacity in Ah
AnalogItemType
If battery voltage is lower than this value, the battery is con-
sidered defective.
PropertyType
When this parameter is set to '1', data from the coded bat-
tery is ignored. The data is taken from the parameter as-
signment in this case.
PropertyType
Battery test interval in hours
Definition
Description
AnalogItemType
Estimated average output current during buffer mode
PropertyType
Trigger voltage for buffering - buffering is activated below
this value
AnalogItemType
Additional buffer time after PC shutdown (valid only in con-
junction with SITOP Manager)
AnalogItemType
Desired buffering time before device switches off
PropertyType
Enable buffering
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76