Connecting Sitop Bat1600 Battery Modules To The Ups Module - Siemens SITOP UPS1600 Equipment Manual

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

7.3

Connecting SITOP BAT1600 battery modules to the UPS module

Up to 6 SITOP BAT1600 battery modules of the same type can be connected in parallel to a
UPS in a star topology.
The maximum permissible cable length between a UPS module and each battery module is
3 m.
The cables and conductors used must be approved for temperatures of at least 60/75 °C.
Note
Use the following minimum cross-sections for the connecting cables/conductors (terminals
"+" and "-") between the UPS module and battery module(s):
• for a 10 A / 20 A system, a minimum cross-section of 2.5 mm
• for a 40 A system, a minimum cross-section of 4 mm
• when connecting the SITOP BAT1600 38 Ah battery module, the minimum cross-section is
6 mm
Longer cable lengths or smaller cross-sections can result in nuisance alarms when buffering!
The following precautionary measures should be carefully taken into account when working
with the battery module and the batteries:
1. Remove watches, rings and other metal objects.
2. Always used tools with insulated handles.
Material damage
It is not permissible that power terminals "+" and "-" are connected to "0V", "GROUND" or the
0V busbar.
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
7.3 Connecting SITOP BAT1600 battery modules to the UPS module
.
2
WARNING
WARNING
.
2
.
2
Installation
213