7.9.3

Replacing batteries in a battery module

The following precautionary measures should be carefully taken into account when working
with the battery module and the batteries:
1. Remove watches, rings and other metal objects.
2. Always used tools with insulated handles.
Note
The batteries cannot be replaced for battery modules with LiFePO4 batteries.
The following battery type is used in battery module SITOP BAT1600:
Battery module
2.5 Ah device
7.5 Ah device
3.2 Ah device:
12 Ah device:
38 Ah device:
Note
In a battery module, always replace all batteries.
Always use the same battery type in a battery module. Before installing new batteries in the
battery module, ensure that all of the batteries have the same charging status.
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
WARNING
Battery types
1 unit
LiFePO4 type: Grepow GRP5970096-25C-25.6V 2800 mAh
3 units
LiFePO4 type: Grepow GRP5970096-25C-25.6V 2800 mAh
2 units
Pb type: YUASA NP3,2-12 or Powerkingdom PS3.2-12
2 units:
Pb type: YUASA NP12-12 or Powerkingdom PS12-12
2 units:
Pb type: YUASA NPL38-12I (FR) or Panasonic P1238APG
7.9 Service life of the batteries and handling
Installation