ABB COM600 Series Operator's Manual page 40

Versatile substation automation and data management unit
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

Figure 3.11.1-1 An example of the Parameter Setting view
40
COM600 series 5.1
Operator's Manual
Click the
icon next to the parameter to open the corresponding help text for each
parameter.
To change parameter settings:
1. Click Enable Write on the top of the Parameter Setting view.
2. Select a new value from the drop-down menu or type in a value in the New Value
field.
If the new values are accepted, the background of the modified parameters turns
green. If the new values are incorrect, a message "Some settings are not in correct
range" is displayed and the background of the modified parameters turns red. Type
in values that are in the correct value range. To apply changes, click Write to IED.
3. To manually update the values, click Refresh Values.
Note that normally Refresh Values will only affect the visible parameters to make
the operation faster. In order to update also hidden (collapsed) parameters, click the
"+" checkbox next to the button. This will cause all parameters to be read, but will
take longer to perform. This checkbox setting is also used when parameters are
refreshed automatically, which happens when the setting group is changed and the
changes are rejected.
4. After you have made all necessary changes, simply click Disable Write if the IED
has not been configured with a store option.
If the IED has been configured with a store option, then either Commit or Reject
must be used instead. Choosing Commit will store the parameter changes perman-
ently to the IED non-volatile memory. Choosing Reject will either cause the para-
meter changes to be reverted directly if the IED supports that, or they are only saved
1MRS756705