  • Page 1 ® Relion 615 Series Motor Protection and Control REM615 ANSI DNP3 Point List Manual...
  • Page 3 Document ID: 1MAC254287-MB Issued: 4/14/2011 Revision: B Product version: 4.0 © Copyright 2011 ABB. All rights reserved.
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
  • Page 6 (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-6 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Section 2 DNP3 data mappings ............9 Overview....................9 Binary/Analog Inputs................. 9 DNP Binary Outputs ................35 Section 3 DNP3 protocol implementation ...........37 DNP3 device profile ................37 DNP3 implementation table ..............40 Section 4 Glossary................45 REM615 ANSI Point List Manual...
  • Page 8 Section 1MAC254287-MB B REM615 ANSI Point List Manual...
  • Page 9: Introduction

    IED perspective. The system engineer or system integrator must have a basic knowledge of communication in protection and control systems and thorough knowledge of the specific communication protocol. REM615 ANSI Point List Manual...
  • Page 10: Product Documentation

    The manual can also be used when calculating settings. The technical manual contains application and functionality descriptions and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data REM615 ANSI Point List Manual...
  • Page 11: Document Revision History

    Product series version History A/01/20/2010 First release B/03/31/2011 Contents updated for 615 series v4.0 ANSI release Download the latest documents from the ABB web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID DNP3 Communication Protocol Manual 1MAC052460-MB Symbols and conventions 1.4.1...
  • Page 12: Manual Conventions

    • IED input/output messages and monitored data names are shown in Courier font, for example: When the function picks up, the PICKUP output is set to TRUE. • Dimensions are provided both in inches and mm. If it is not specifically mentioned then the dimension is in mm. REM615 ANSI Point List Manual...
  • Page 13: Functions, Codes And Symbols

    ARC (2) Arc protection, instance 3 ARCSARC3 AFD-3 ARC (3) Control Circuit-breaker control, instance 1 CBCBR1 I <-> O CB (1) Emergency startup ESMGAPC1 62EST ESTART Condition Monitoring Circuit-breaker condition monitoring, instance 1 SSCBR1 52CM CBCM(1) REM615 ANSI Point List Manual...
  • Page 14 Set reset (8 pcs), instance 1 SRGAPC1 SR-1 SR (1) Set reset (8 pcs), instance 2 SRGAPC2 SR-2 SR (2) Move (8 pcs), instance 1 MVGAPC1 MV-1 MV (1) Move (8 pcs), instance 2 MVGAPC2 MV-2 MV (2) REM615 ANSI Point List Manual...
  • Page 15: Dnp3 Data Mappings

    Section 2 DNP3 data mappings Overview This document describes the DNP3 data points and structures available in REM615 Ver. 4.0 ANSI. The point tables show all the available DNP3 data points in this IED. The data objects in the point tables are listed based on the IEC61850 logical node name. Also the default point indexes, class assignments and scaling configurations are shown.
  • Page 16 X110-Input 2 BIO LD0.XGGIO110.Ind2.stVal Class 1 and 0 X110-Input 3 BIO LD0.XGGIO110.Ind3.stVal Class 1 and 0 X110-Input 4 BIO LD0.XGGIO110.Ind4.stVal Class 1 and 0 X110-Input 5 BIO LD0.XGGIO110.Ind5.stVal Class 1 and 0 X110-Input 6 BIO LD0.XGGIO110.Ind6.stVal REM615 ANSI Point List Manual...
  • Page 17 51P Phase A Trip (Operate) LD0.PHLPTOC1.Op.phsA Class 1 and 0 51P Phase B Trip (Operate) LD0.PHLPTOC1.Op.phsB Class 1 and 0 51P Phase C Trip (Operate) LD0.PHLPTOC1.Op.phsC Class 0 51P Enable Signal For Current Multiplier LD0.PHLPTOC1.InEnaMult.stVal REM615 ANSI Point List Manual...
  • Page 18 Class 1 and 0 27 Trip (Operate) LD0.PHPTUV1.Op.general Class 1 and 0 27 Phase A Trip (Operate) LD0.PHPTUV1.Op.phsA Class 1 and 0 27 Phase B Trip (Operate) LD0.PHPTUV1.Op.phsB Class 1 and 0 27 Phase C Trip (Operate) LD0.PHPTUV1.Op.phsC REM615 ANSI Point List Manual...
  • Page 19 Enabled Description IEC61850 Data Attribute Name Event Index Factor Type Class 1 and 0 81 Under-Frequency Trip (Operate) LD0.FRPTUF1.Op.general Class 0 81 Ratio Of Pickup (Start) Time / Trip LD0.FRPTUF1.StrDur.mag.f (Operate) Time Underfrequency Instance 1 REM615 ANSI Point List Manual...
  • Page 20 51LR Motor Jam Phase C Trip (Operate) LD0.JAMPTOC1.Op.phsC Table 30: 66/51LRS:Motor start-up supervision (STTPMSS1) Point Scale Object DNP Class Enabled Description IEC61850 Data Attribute Name Event Index Factor Type Class 1 and 0 66/51LRS Trip (Operate)/Trip Signal For LD0.STTPMSS1.Op.general Stalling Protection REM615 ANSI Point List Manual...
  • Page 21 87M Motor Differential Protection Block LD0.MPDIF1.BlkInSt.general Class 0 87M Motor Differential Protection Block LD0.MPDIF1.BlkInSt.phsA Phase A Class 0 87M Motor Differential Protection Block LD0.MPDIF1.BlkInSt.phsB Phase B Class 0 87M Motor Differential Protection Block LD0.MPDIF1.BlkInSt.phsC Phase C REM615 ANSI Point List Manual...
  • Page 22 AFD-1 Remote Fault Arc Detected 1 LD0.ARCSARC11.InRemFA.stVa Table 39: AFD-1:Arc protection-instance 1 (ARCPTRC11) Point Scale Object DNP Class Enabled Description IEC61850 Data Attribute Name Event Index Factor Type Class 1 and 0 AFD-1 Arc Detected Trip (Operate) 1 LD0.ARCPTRC11.Op.general REM615 ANSI Point List Manual...
  • Page 23 Index Factor Type Class 1 and 0 52 Breaker Interlock Enable Open 1 CTRL.CBCILO1.EnaOpn.stVal Class 1 and 0 52 Breaker Interlock Enable Close 1 CTRL.CBCILO1.EnaCls.stVal Class 1 and 0 52 Breaker Interlock Bypass 1 CTRL.CBCILO1.ItlByPss.stVal REM615 ANSI Point List Manual...
  • Page 24 52CM Recloser Open Travel Time LD0.SSCBR1.OpnAlm.stVal Exceeded Set Value 1 Class 1 and 0 52CM Recloser Close Travel Time LD0.SSCBR1.ClsAlm.stVal Exceeded Set Value 1 Class 1 and 0 52CM Spring Charging Time Has LD0.SSCBR1.SprChaAlm.stVal Crossed The Set Value 1 REM615 ANSI Point List Manual...
  • Page 25 Remaining Life 1 Class 0 52CM Phase A Accumulated Currents LD0.SSCBR1.AccAPwrPhA.mag.f Power (Iyt) 1 Class 0 52CM Phase B Accumulated Currents LD0.SSCBR1.AccAPwrPhB.mag.f Power (Iyt) 1 Class 0 52CM Phase C Accumulated Currents LD0.SSCBR1.AccAPwrPhC.mag.f Power (Iyt) 1 REM615 ANSI Point List Manual...
  • Page 26 Index Factor Type Class 1 and 0 OPTM-2 Motor Runtime Counter LD0.MDSOPT2.OpTmWrn.stVal Operation Time Warning 2 Class 1 and 0 OPTM-2 Motor Runtime Counter LD0.MDSOPT2.OpTmAlm.stVal Operation Time Alarm 2 Class 0 OPTM-2 operation t LD0.MDSOPT2.OpTmRs.stVal REM615 ANSI Point List Manual...
  • Page 27 IA IB IC (2) Phase A Mag (RMS) LD0.CMMXU2.A.phsA.instCVal.m ag.f Class 2 and 0 IA IB IC (2) Phase A Mag LD0.CMMXU2.A.phsA.cVal.mag.f (Deadbanded) Class 2 and 0 IA IB IC (2) Phase B Mag (RMS) LD0.CMMXU2.A.phsB.instCVal.m ag.f REM615 ANSI Point List Manual...
  • Page 28 Class 2 and 0 I1-I2-I0 (1) Negative Sequence LD0.CSMSQI1.SeqA.c2.cVal.mag Magnitude (Deadband) Class 2 and 0 I1-I2-I0 (1) Zero Sequence Magnitude LD0.CSMSQI1.SeqA.c3.instCVal. (RMS) mag.f Class 2 and 0 I1-I2-I0 (1) Zero Sequence Magnitude LD0.CSMSQI1.SeqA.c3.cVal.mag (Deadband) REM615 ANSI Point List Manual...
  • Page 29 Class 2 and 0 VA VB VC Phase BC Mag LD0.VMMXU1.PPV.phsBC.cVal.mag.f (Deadband) Class 2 and 0 VA VB VC Phase CA Mag LD0.VMMXU1.PPV.phsCA.instCVal.mag.f (RMS) Class 2 and 0 VA VB VC Phase CA Mag LD0.VMMXU1.PPV.phsCA.cVal.mag.f (Deadband) REM615 ANSI Point List Manual...
  • Page 30 Class 2 and 0 SP SE Average A Power Factor 1 LD0.SPEMMXU1.PF.phsA.cVal.mag.f Class 2 and 0 SP SE Average B Power Factor 1 LD0.SPEMMXU1.PF.phsB.cVal.mag.f Class 2 and 0 SP SE Average C Power Factor 1 LD0.SPEMMXU1.PF.phsC.cVal.mag.f REM615 ANSI Point List Manual...
  • Page 31 TP - 3 In2/Out2 LD0.TPGAPC3.Op.general Table 77: TP - 4:Minimum pulse timer (2 pcs)-instance 4 (TPGAPC4) Point Scale Object DNP Class Enabled Description IEC61850 Data Attribute Name Event Index Factor Type Class 0 TP - 4 In2/Out2 LD0.TPGAPC4.Op.general REM615 ANSI Point List Manual...
  • Page 32 Class 0 PT-2 Generic Pulse Timer 2 Input LD0.PTGAPC2.In3.stVal Class 0 PT-2 Generic Pulse Timer 2 Input LD0.PTGAPC2.In4.stVal Class 0 PT-2 Generic Pulse Timer 2 Input LD0.PTGAPC2.In5.stVal Class 0 PT-2 Generic Pulse Timer 2 Input LD0.PTGAPC2.In6.stVal REM615 ANSI Point List Manual...
  • Page 33 Input 8 Class 0 TOF-1 Generic Time Delay Off 1 LD0.TOFGAPC1.Q1.stVal Output 1 Class 0 TOF-1 Generic Time Delay Off 1 LD0.TOFGAPC1.Q2.stVal Output 2 Class 0 TOF-1 Generic Time Delay Off 1 LD0.TOFGAPC1.Q3.stVal Output 3 REM615 ANSI Point List Manual...
  • Page 34 Output 5 Class 0 TOF-2 Generic Time Delay Off 2 LD0.TOFGAPC2.Q6.stVal Output 6 Class 0 TOF-2 Generic Time Delay Off 2 LD0.TOFGAPC2.Q7.stVal Output 7 Class 0 TOF-2 Generic Time Delay Off 2 LD0.TOFGAPC2.Q8.stVal Output 8 REM615 ANSI Point List Manual...
  • Page 35 Class 0 TON -2 Generic Time Delay On 2 LD0.TONGAPC2.In2.stVal Input 2 Class 0 TON -2 Generic Time Delay On 2 LD0.TONGAPC2.In3.stVal Input 3 Class 0 TON -2 Generic Time Delay On 2 LD0.TONGAPC2.In4.stVal Input 4 REM615 ANSI Point List Manual...
  • Page 36 SR-1 Set 4 Set-Reset Flip Flop - 1 LD0.SRGAPC1.Set4.stVal Class 0 SR-1 Set 5 Set-Reset Flip Flop - 1 LD0.SRGAPC1.Set5.stVal Class 0 SR-1 Set 6 Set-Reset Flip Flop - 1 LD0.SRGAPC1.Set6.stVal Class 0 SR-1 Set 7 Set-Reset Flip Flop - 1 LD0.SRGAPC1.Set7.stVal REM615 ANSI Point List Manual...
  • Page 37 IEC61850 Data Attribute Name Event Index Factor Type Class 0 MV-2 Gen. Purp. 2 Trip (Operate) LD0.MVGAPC2.Op.general Class 1 and 0 MV-2 Gen. Purp. Q9 LD0.MVGAPC2.Q1.stVal Class 1 and 0 MV-2 Gen. Purp. Q10 LD0.MVGAPC2.Q2.stVal REM615 ANSI Point List Manual...
  • Page 38 Class 2 and 0 Bias current phase C LD0.FLTMSTA1.RstAmpsC.mag.f Class 2 and 0 Differential current residual LD0.FLTMSTA1.DifAmpsN.mag.f Class 2 and 0 Bias current residual LD0.FLTMSTA1.RstAmpsN.mag.f Class 2 and 0 Last Fault: Max Phase A Current LD0.FLTMSTA1.MaxAmpsA.mag.f Magnitude REM615 ANSI Point List Manual...
  • Page 39 LD0.FLTMSTA1.VoltsAB.mag.f Magnitude Class 2 and 0 Last Fault: Phase BC Voltage LD0.FLTMSTA1.VoltsBC.mag.f Magnitude Class 2 and 0 Last Fault: Phase CA Voltage LD0.FLTMSTA1.VoltsCA.mag.f Magnitude Class 2 and 0 Last Fault: Measured Residual LD0.FLTMSTA1.VoltsN.mag.f Voltage Magnitude REM615 ANSI Point List Manual...
  • Page 40 FLO:Fault location (DRFLO1) Point Scale Object DNP Class Enabled Description IEC61850 Data Attribute Name Event Index Factor Type Class 0 FLO Relay Trip LD0.DRFLO1.Tr.general Class 2 and 0 FLO Distance to fault measured in LD0.DRFLO1.FltDisKm.mag.f Km/Miles REM615 ANSI Point List Manual...
  • Page 41: Dnp Binary Outputs

    X110-Output 3 LD0.XGGIO110.SPCSO3.Oper.ctlVal X110-Output 4 LD0.XGGIO110.SPCSO4.Oper.ctlVal X100-Output 1 LD0.XGGIO100.SPCSO1.Oper.ctlVal X100-Output 2 LD0.XGGIO100.SPCSO2.Oper.ctlVal X100-Output 3 LD0.XGGIO100.SPCSO3.Oper.ctlVal X100-Output 4 LD0.XGGIO100.SPCSO4.Oper.ctlVal X100-Output 5 LD0.XGGIO100.SPCSO5.Oper.ctlVal X100-Output 6 LD0.XGGIO100.SPCSO6.Oper.ctlVal Led 1 Control LD0.LEDGGIO1.SPCSO1.Oper.ctlVa Led 2 Control LD0.LEDGGIO1.SPCSO2.Oper.ctlVa Led 3 Control LD0.LEDGGIO1.SPCSO3.Oper.ctlVa REM615 ANSI Point List Manual...
  • Page 42 LD0.TRPPTRC1.TrRs.Oper.ctlVal 86/94-2 Clear Lockout Master Trip 2 LD0.TRPPTRC2.LORs.Oper.ctlVal 86/94-2 Clear Master Trip2 LD0.TRPPTRC2.TrRs.Oper.ctlVal OPTM-1 Clear operation time LD0.MDSOPT1.OpTmRs.Oper.ctlVal OPTM-2 Clear operation time LD0.MDSOPT2.OpTmRs.Oper.ctlVal 66/51LRS Reset number of motor LD0.STTPMRI1.RsStUpCnt.Oper.ctl start-ups counter 49M Clear temperature LD0.MPTTR1.RsTmp.Oper.ctlVal REM615 ANSI Point List Manual...
  • Page 43: Dnp3 Protocol Implementation

    Definitions as a document, it is in fact a table, and only a component of a total interoperability guide. The table, in combination with the Implementation table and the point list tables provides a complete configuration/interoperability guide for communicating with a device. REM615 ANSI Point List Manual...
  • Page 44 Select/Operate Arm Timeout, not configurable; fixed at 10s, regardless of select timeout in the HMI. Need time interval, configurable Unsolicited notification delay, configurable Unsolicited response retry delay, configurable Unsolicited offline Interval, configurable Sends/Executes Control Operations: REM615 ANSI Point List Manual...
  • Page 45 No counters reported ○ Configurable ○ Configurable (attach explanation) ○ Default object ○ 16 bits Default variation: ○ Point-by-point list attached ○ 32 bits ○ Other value: _______ ○ Point-by-point list attached Sends multi-fragment responses: ● ○ REM615 ANSI Point List Manual...
  • Page 46: Dnp3 Implementation Table

    07, 08 (limited qty) 130 (unsol. resp) change without time Binary 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) input 07, 08 (limited qty) 130 (unsol. resp) change with time REM615 ANSI Point List Manual...
  • Page 47 07, 08 (limited qty) 130 (unsol. resp) change event without time 32-bit 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) analog 07, 08 (limited qty) 130 (unsol. resp) change event with time REM615 ANSI Point List Manual...
  • Page 48 1. A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Default variations are configurable; however, default settings for the configuration parameters are indicated in the table above. REM615 ANSI Point List Manual...
  • Page 49 17 or 28 are always responded.) 3. Writes of internal indications are only supported for index 7 (Restart IIN1-7) 4. Cold and warm restarts return an application layer acknowledge, but no restart action is taken. REM615 ANSI Point List Manual...
  • Page 50 Section 3 1MAC254287-MB B DNP3 protocol implementation REM615 ANSI Point List Manual...
  • Page 51: Glossary

    International standard for substation communication and modelling Intelligent electronic device Logical device zero (0) Light-emitting diode LHMI Local human-machine interface LLN0 Logical node zero (0) PCM600 Protection and Control IED Manager Power supply module Select-before-operate stVal Status value REM615 ANSI Point List Manual...
  • Page 52 Section 4 1MAC254287-MB B Glossary Value REM615 ANSI Point List Manual...
  • Page 54 Contact us ABB Inc. Distribution Automation 4300 Coral Ridge Drive Coral Springs, FL 33065, USA Phone:+1 (800) 523-2620 Phone:+1 954-752-6700 Fax:+1 954 345-5329 www.abb.com/substationautomation...