  • Page 1 Relion 615 ® series Motor protection and control REM615 ANSI Product guide...
  • Page 2 16 Access control ......12 Disclaimer Th e information in this document is subject to change without notice and should not be construed as a commitment by ABB Inc. ABB Inc. assumes no responsibility for any errors that may appear in this document.
  • Page 3: Description

    Th e main features of the motor IED include thermal REM615 is a member of ABB’s Relion® product family overload protection, motor start-up time supervision, and a part of its 615 protection and control product locked rotor protection, and protection against series.
  • Page 4: Standard Confi Gurations

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 One confi guration comprises only current analog inputs 2. Standard useful in cost-eff ective motor protection, control and confi gurations monitoring industrial and utility applications. Th e second...
  • Page 5 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 2. Functions and features 3 CT + Ground 3 CT + Ground Analog Inputs CT + 5 VT Included = •, Optional =  Order Code...
  • Page 6: Protection Functions

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 3. Protection functions Th e REM615 also incorporates non-directional and directional earth-fault protection, backup overcurrent Th e REM615 relay off ers all the functionality needed protection, three phase undervoltage protection, and...
  • Page 7: Application

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Th e motor relay is thoroughly adapted for ground fault 4. Application protection. Using cable current transformers, sensitive and reliable ground fault protection can be achieved. Th e ground fault protection can also utilize phase current...
  • Page 8: Supported Abb Solutions

    COM600 features a web-browser based HMI providing a customizable graphical display for visualizing single line mimic ABB’s 615 series protection and control IEDs diagrams for switchgear design solutions. To together with the COM600 Station Automation enhance personnel safety, the web HMI also enables device constitute a genuine IEC 61850 solution for remote access to substation devices and processes.
  • Page 9 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 MicroSCADA IEC 60870-5-104 COM600 COM600 Web HMI Web HMI COM600 COM600 Ethernet switch PCM600 Ethernet switch PCM600 Peer-to-peer IEC 61850-8-1 Peer-to-peer IEC 61850-8-1 GOOSE communication GOOSE communication...
  • Page 10: Control

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 6. Control be set to start a recording on the rising or the falling edge of the binary signal or both. Th e relay off ers status and control of one circuit...
  • Page 11: Self-Diagnostics

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 11. Circuit-breaker 14. Fuse failure condition monitoring protection For continuous knowledge of the operational Depending on the chosen standard confi guration, the availability of the REM615 features, a comprehensive IED includes fuse failure supervision functionality.
  • Page 12: Access Control

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Th e binary input turn-on thresholds are programmable 16. Access control from 18…176 V DC by adjusting the relay’s param- eter settings. All binary input and output contacts are freely programmable with the signal matrix tool in the REM615 PCM600 soft ware user tool.
  • Page 13: Communication

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Modbus over TCP/IP is supported with the Ethernet 18. Communication communications option selected. Besides standard Modbus functionality such as status and control operations, the relay supports retrieval of time-stamped...
  • Page 14: Technical Data

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 19. Technical data Table 6. Dimensions Description Value Width frame 7.08” (179.8 mm) case 6.46” (164 mm) Height frame 6.97 (177 mm), 4U case 6.30” (160 mm)
  • Page 15 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 8. Analog inputs Value Description Rated frequency 60/50 Hz ± 5 Hz Current inputs Rated current, I 5/1 A 0.2 A Th ermal withstand capability: • Continuously 20 A •...
  • Page 16 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 12. Self-diagnostics alarm signal output (SO) [Typical operation time: 5...8 ms] Value Description 250 V AC/DC Rated voltage Continuous contact carry Make and carry for 3.0 s 10 A Make and carry 0.5 s...
  • Page 17 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 16. Degree of protection of fl ush-mounted relay Description Value IP 54 Front side Back side, connection terminals IP 20 Table 17. Environmental conditions Description Value Continuous operating temperature range -25 C to +55°...
  • Page 18 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 19. Electromagnetic compatibility tests Th e EMC immunity test level meets the requirements listed below: Description Type test value Reference 1 MHz burst disturbance test, class III:...
  • Page 19 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 19. Electromagnetic compatibility tests (continued) Th e EMC immunity test level meets the requirements listed below: Description Value Electromagnetic emission tests: According to the EN 55011, class A and IEC60255-25 •...
  • Page 20 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 23. Product safety Complies with the LV directive 2006/95/EC Standards EN 60255-27 (2005), EN 60255-6 (1994) Table 24. RoHS compliance Complies with the RoHS directive 2002/95/EC Table 25.
  • Page 21 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 27. Th ree-phase non-directional overcurrent protection (50P, 51P) main settings Parameter Function Value (Range) Step Pickup range 0.05...5.00 x I 0.01 0.10...40.00 x I 0.01 Time multiplier 0.8...10.0...
  • Page 22 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 29. Non-directional ground fault protection (51G) main settings Parameter Function Value (Range) Step Pickup range 0.05...5.00 x I 0.01 Time multiplier 0.05...15.00 0.05 Defi nite time delay 40...200000 ms...
  • Page 23 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 31. Directional ground fault protection (67/51N) main settings Parameter Function Value (Range) Step Pickup range 67/51N 0.05...5.00 x I 0.01 Directional mode 67/51N 1=Non-directional 2=Forward 3=Reverse...
  • Page 24 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 33. Th ree-phase overvoltage protection (59) main settings Parameter Function Value (Range) Step Pickup range 0.05...1.60 x U 0.01 Time multiplier 0.05...15.00 0.05 Defi nite time delay 40...300000 ms...
  • Page 25 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 36. Positive sequence undervoltage protection (27PS) Characteristic Value Pickup Depending on the frequency of the voltage accuracy measured: fn ±2Hz ±1.5% of the set value or ±0.002 x U...
  • Page 26 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 39. Negative sequence overvoltage protection (47) main settings Parameter Function Value (Range) Step Pickup range 0.010...1.000 x U 0.001 Defi nite time delay 40...120000 ms Table 40. Ground overvoltage protection (59G)
  • Page 27 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 43. Negative phase-sequence current protection (46) main settings Parameter Function Value (Range) Step Pickup range 0.01...5.00 x I 0.01 Time multiplier 0.05...15.00 0.05 Defi nite time delay 40...200000 ms...
  • Page 28 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 48. Motor start-up supervision (66/51LRS) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: fn ±2Hz ±1.5% of the set value or ±0.002 x U...
  • Page 29 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 51. Th ree-phase thermal overload protection for motors (49M) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: fn ±2Hz Current measurement: ±1.5% of the set value or ±0.002 x In (at currents in the range of...
  • Page 30 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 55. Arc protection (AFD) Characteristic Value ±3% of the set value or ±0.01 x I Pickup Accuracy Trip time Minimum Typical Maximum Operation mode = “Light+current”...
  • Page 31 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 60. Th ree-phase voltage measurements (VA, VB, VC) Characteristic Value Pickup Depending on the frequency of the voltage measured: fn ±2Hz accuracy (at voltages in range 0.01...1.15 x Un) ±0.5% or ±0.002 x U...
  • Page 32 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Supervision functions Table 65. Current circuit supervision (CCM) Characteristic Value Trip time < 30 ms Including the delay of the output contact Table 66. Current circuit supervision (CCM) main settings...
  • Page 33 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 20. Display The relay’s local HMI includes a large LCD screen Th e large display off ers increased front-panel usability standard. Th e large LCD display off ers full front-panel...
  • Page 34: Mounting Methods

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 21. Mounting methods 22. Relay case and drawout unit By means of appropriate mounting accessories the standard relay case for the 615 series relays can be fl ush For safety reasons, the relay cases are provided with mounted, semi-fl ush mounted or wall mounted.
  • Page 35: Selection And Ordering Data

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 23. Selection and Use the ordering key information in Fig. 10 to generate ordering data the order number when ordering complete protection relays. The relay type and serial number label identifies t h e p r o t e c t i o n r e l a y.
  • Page 36: Accessories And Ordering Data

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 24. Accessories and ordering data Table 70. Accessories and ordering data. Item Order Number Tools PCM600 V2.0 user tool PCM600-20 Cables Cable for optical sensors for arc protection 1.5 m 1MRS120534-1.5...
  • Page 37: Tools

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 When the web-browser based user interface is used, the 25. Tools relay can be accessed either locally or remotely using a web browser (IE 6.0 or later). For security reasons, the web-browser based user interface is disabled by default.
  • Page 38: Terminal Diagrams

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 26. Terminal diagrams REM615 ANSI X100 X120 BI 1 BI 2 BI 3 BI 4 X130 TCM-1 BI 1 BI 2 TCM-2 BI 3 BI 4 X110...
  • Page 39: Terminal Diagrams

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 REM615 ANSI X100 X120 BI 1 BI 2 BI 3 BI 4 X130 BI 1 BI 2 TCM-1 BI 3 BI 4 TCM-2 Not in use X110...
  • Page 40: Certifi Cates

    Th e Features and Application tabs contain product related information in a compact format. Th e www.abb.com/substationautomation portal off ers you information about the distribution automation product and service range. You will fi nd the latest relevant information on the REM615 protection relay on the product page.
  • Page 41: Functions, Codes And Symbols

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 29. Functions, codes and symbols Table 72. REM615 Functions, codes and symbols Function IEC 61850 ANSI C37.2-2008 Protection PHLPTOC Th ree-phase non-directional time overcurrent Th ree-phase non-directional instantaneous overcurrent, low-set,...
  • Page 42: Functions, Codes And Symbols

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 72. REM615 Functions, codes and symbols (continued) Function IEC 61850 ANSI C37.2-2008 Measurement Digital fault recorder (DFR) RDRE1 Th ree-phase currents CMMXU1 IA, IB, IC Sequence currents...
  • Page 43: Document Revision History

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 30. Document revision history Table 73. Document revision history A/ March 01, 2010 V2.0 Initial product version release...
  • Page 44: Notes

    Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 31. Notes...
  • Page 45 Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0...
  • Page 46 Contact us ABB Inc. All sales are subject to ABB Inc. Distribution Automation General Terms and Conditions of Sale. 4300 Coral Ridge Drive Coral Springs, Florida 33065 While every effort has been made to Phone: +1 954-752-6700 assure accuracy, the information in this...