Page 1
Relion 615 ® series Motor protection and control REM615 ANSI Product guide...
Page 2
16 Access control ......12 Disclaimer Th e information in this document is subject to change without notice and should not be construed as a commitment by ABB Inc. ABB Inc. assumes no responsibility for any errors that may appear in this document.
Th e main features of the motor IED include thermal REM615 is a member of ABB’s Relion® product family overload protection, motor start-up time supervision, and a part of its 615 protection and control product locked rotor protection, and protection against series.
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 One confi guration comprises only current analog inputs 2. Standard useful in cost-eff ective motor protection, control and confi gurations monitoring industrial and utility applications. Th e second...
Page 5
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 2. Functions and features 3 CT + Ground 3 CT + Ground Analog Inputs CT + 5 VT Included = •, Optional = Order Code...
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 3. Protection functions Th e REM615 also incorporates non-directional and directional earth-fault protection, backup overcurrent Th e REM615 relay off ers all the functionality needed protection, three phase undervoltage protection, and...
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Th e motor relay is thoroughly adapted for ground fault 4. Application protection. Using cable current transformers, sensitive and reliable ground fault protection can be achieved. Th e ground fault protection can also utilize phase current...
COM600 features a web-browser based HMI providing a customizable graphical display for visualizing single line mimic ABB’s 615 series protection and control IEDs diagrams for switchgear design solutions. To together with the COM600 Station Automation enhance personnel safety, the web HMI also enables device constitute a genuine IEC 61850 solution for remote access to substation devices and processes.
Page 9
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 MicroSCADA IEC 60870-5-104 COM600 COM600 Web HMI Web HMI COM600 COM600 Ethernet switch PCM600 Ethernet switch PCM600 Peer-to-peer IEC 61850-8-1 Peer-to-peer IEC 61850-8-1 GOOSE communication GOOSE communication...
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 6. Control be set to start a recording on the rising or the falling edge of the binary signal or both. Th e relay off ers status and control of one circuit...
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 11. Circuit-breaker 14. Fuse failure condition monitoring protection For continuous knowledge of the operational Depending on the chosen standard confi guration, the availability of the REM615 features, a comprehensive IED includes fuse failure supervision functionality.
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Th e binary input turn-on thresholds are programmable 16. Access control from 18…176 V DC by adjusting the relay’s param- eter settings. All binary input and output contacts are freely programmable with the signal matrix tool in the REM615 PCM600 soft ware user tool.
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Modbus over TCP/IP is supported with the Ethernet 18. Communication communications option selected. Besides standard Modbus functionality such as status and control operations, the relay supports retrieval of time-stamped...
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 19. Technical data Table 6. Dimensions Description Value Width frame 7.08” (179.8 mm) case 6.46” (164 mm) Height frame 6.97 (177 mm), 4U case 6.30” (160 mm)
Page 15
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 8. Analog inputs Value Description Rated frequency 60/50 Hz ± 5 Hz Current inputs Rated current, I 5/1 A 0.2 A Th ermal withstand capability: • Continuously 20 A •...
Page 16
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 12. Self-diagnostics alarm signal output (SO) [Typical operation time: 5...8 ms] Value Description 250 V AC/DC Rated voltage Continuous contact carry Make and carry for 3.0 s 10 A Make and carry 0.5 s...
Page 17
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 16. Degree of protection of fl ush-mounted relay Description Value IP 54 Front side Back side, connection terminals IP 20 Table 17. Environmental conditions Description Value Continuous operating temperature range -25 C to +55°...
Page 18
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 19. Electromagnetic compatibility tests Th e EMC immunity test level meets the requirements listed below: Description Type test value Reference 1 MHz burst disturbance test, class III:...
Page 19
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 19. Electromagnetic compatibility tests (continued) Th e EMC immunity test level meets the requirements listed below: Description Value Electromagnetic emission tests: According to the EN 55011, class A and IEC60255-25 •...
Page 20
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 23. Product safety Complies with the LV directive 2006/95/EC Standards EN 60255-27 (2005), EN 60255-6 (1994) Table 24. RoHS compliance Complies with the RoHS directive 2002/95/EC Table 25.
Page 21
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 27. Th ree-phase non-directional overcurrent protection (50P, 51P) main settings Parameter Function Value (Range) Step Pickup range 0.05...5.00 x I 0.01 0.10...40.00 x I 0.01 Time multiplier 0.8...10.0...
Page 22
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 29. Non-directional ground fault protection (51G) main settings Parameter Function Value (Range) Step Pickup range 0.05...5.00 x I 0.01 Time multiplier 0.05...15.00 0.05 Defi nite time delay 40...200000 ms...
Page 23
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 31. Directional ground fault protection (67/51N) main settings Parameter Function Value (Range) Step Pickup range 67/51N 0.05...5.00 x I 0.01 Directional mode 67/51N 1=Non-directional 2=Forward 3=Reverse...
Page 24
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 33. Th ree-phase overvoltage protection (59) main settings Parameter Function Value (Range) Step Pickup range 0.05...1.60 x U 0.01 Time multiplier 0.05...15.00 0.05 Defi nite time delay 40...300000 ms...
Page 25
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 36. Positive sequence undervoltage protection (27PS) Characteristic Value Pickup Depending on the frequency of the voltage accuracy measured: fn ±2Hz ±1.5% of the set value or ±0.002 x U...
Page 26
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 39. Negative sequence overvoltage protection (47) main settings Parameter Function Value (Range) Step Pickup range 0.010...1.000 x U 0.001 Defi nite time delay 40...120000 ms Table 40. Ground overvoltage protection (59G)
Page 27
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 43. Negative phase-sequence current protection (46) main settings Parameter Function Value (Range) Step Pickup range 0.01...5.00 x I 0.01 Time multiplier 0.05...15.00 0.05 Defi nite time delay 40...200000 ms...
Page 28
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 48. Motor start-up supervision (66/51LRS) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: fn ±2Hz ±1.5% of the set value or ±0.002 x U...
Page 29
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 51. Th ree-phase thermal overload protection for motors (49M) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: fn ±2Hz Current measurement: ±1.5% of the set value or ±0.002 x In (at currents in the range of...
Page 30
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 55. Arc protection (AFD) Characteristic Value ±3% of the set value or ±0.01 x I Pickup Accuracy Trip time Minimum Typical Maximum Operation mode = “Light+current”...
Page 31
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Table 60. Th ree-phase voltage measurements (VA, VB, VC) Characteristic Value Pickup Depending on the frequency of the voltage measured: fn ±2Hz accuracy (at voltages in range 0.01...1.15 x Un) ±0.5% or ±0.002 x U...
Page 32
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 Supervision functions Table 65. Current circuit supervision (CCM) Characteristic Value Trip time < 30 ms Including the delay of the output contact Table 66. Current circuit supervision (CCM) main settings...
Page 33
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 20. Display The relay’s local HMI includes a large LCD screen Th e large display off ers increased front-panel usability standard. Th e large LCD display off ers full front-panel...
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 21. Mounting methods 22. Relay case and drawout unit By means of appropriate mounting accessories the standard relay case for the 615 series relays can be fl ush For safety reasons, the relay cases are provided with mounted, semi-fl ush mounted or wall mounted.
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 23. Selection and Use the ordering key information in Fig. 10 to generate ordering data the order number when ordering complete protection relays. The relay type and serial number label identifies t h e p r o t e c t i o n r e l a y.
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 24. Accessories and ordering data Table 70. Accessories and ordering data. Item Order Number Tools PCM600 V2.0 user tool PCM600-20 Cables Cable for optical sensors for arc protection 1.5 m 1MRS120534-1.5...
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 When the web-browser based user interface is used, the 25. Tools relay can be accessed either locally or remotely using a web browser (IE 6.0 or later). For security reasons, the web-browser based user interface is disabled by default.
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 26. Terminal diagrams REM615 ANSI X100 X120 BI 1 BI 2 BI 3 BI 4 X130 TCM-1 BI 1 BI 2 TCM-2 BI 3 BI 4 X110...
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 REM615 ANSI X100 X120 BI 1 BI 2 BI 3 BI 4 X130 BI 1 BI 2 TCM-1 BI 3 BI 4 TCM-2 Not in use X110...
Th e Features and Application tabs contain product related information in a compact format. Th e www.abb.com/substationautomation portal off ers you information about the distribution automation product and service range. You will fi nd the latest relevant information on the REM615 protection relay on the product page.
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 30. Document revision history Table 73. Document revision history A/ March 01, 2010 V2.0 Initial product version release...
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0 31. Notes...
Page 45
Motor Protection 1MAC251744 -PG Rev. A REM615 ANSI Issued: 03.01.2010 Product Version 2.0...
Page 46