P R O D U C T G U I D E
REM615 ANSI 5.0 FP1
Motor protection and control

Advertisement

Table of Contents
loading

Summary of Contents for ABB REM615 ANSI 5.0 FP1

  • Page 1 — P R O D U C T G U I D E REM615 ANSI 5.0 FP1 Motor protection and control...
  • Page 2: Table Of Contents

    2. Standard configuration 18-22 18. Station communication 10-12 3. Protection functions 23-42 19. Technical data 4. Application 20. Local HMI 5. Supported ABB 21. Mounting methods solutions 22. Relay case and plug-in 6. Control unit 7. Measurement 23. Selection and ordering data 8.
  • Page 3: Description

    REM615 is a trix or the graphical application functionality of the member of ABB’s Relion® product family and part Protection and Control IED Manager PCM600. Fur- of its 615 protection and control product series.
  • Page 4 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L — Figure 1. Functionality overview for standard configuration A REM615 V5.0 FP1 ANSI Func Appl A...
  • Page 5 — Figure 2. Functionality overview for standard configuration B Υ or Δ REM615 V5.0 FP1 ANSI Func Appl B 27-1 27PS 47-1 81-1 81-2 50P-1 51LR-1 51LRS 46M-1 46M-2 37M-1 50P-3 50G-1 AFD- AFD- AFD- Available with Arc Flash Detection (AFD) option Available with RTD option...
  • Page 6 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L — Figure 3. Functionality overview for standard configuration D Va, Vb, Vc...
  • Page 7 — Figure 4. Functionality overview for standard configuration E Δ Υ or Δ REM615 V5.0 FP1 ANSI Func Appl E 27-2 27-1 27PS 47-1 59-1 81-1 47-2 50P-3 50P-1 51LR-1 51LR-2 51LRS 59N-1 59G-1 59-2 46M-1 46M-2 50P-2 81-2 32O-1 32O-2 32O-3 32U-1...
  • Page 8: Description

    R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L — Table 1. Standard configurations Description Std.
  • Page 9 — Table 2. Supported functions (continued) Function IEC 61850 ANSI Control Earthing switch indication ESSXSWI 29GS (19) (19) (19) (19) Emergency startup ESMGAPC 62EST Conditioning monitoring and supervision Circuit breaker condition monitoring SSCBR 52CM Trip circuit supervision TCSSCBR Current circuit supervision CCSPVC Fuse failure supervision SEQSPVC...
  • Page 10: Protection Functions

    R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L 14) IoB measured and 3IB are always used 15) Io measured is always used 16) IoB selectable by parameter, IoB measured as default 17) Power quality option includes Current total demand distortion, Voltage total harmonic distortion and Voltage variation.
  • Page 11 The standard configuration D includes one conven- the use of the relay in compact medium voltage tional residual current (Io) input and three com- switchgears, such as ABB’s ReliaGear® ND Digital, bi-sensor inputs for phase currents and phase volt- Advance Digital and SafeGear Digital, with limited ages.
  • Page 12 (voltage divider) are The standard configuration D has been pre- used for the measurements. To prevent possible configured especially for ABB switchgears, for power system instability due to busbar voltage example, Advance Digital. The use of this...
  • Page 13: Supported Abb Solutions

    615 series relays distribution in utility and industrial power systems. without the optional single-line diagram feature are To facilitate the system engineering, ABB's relays used. The Web HMI of COM600F also provides an are supplied with connectivity packages. The...
  • Page 14: Control

    R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L Figure 7. ABB power...
  • Page 15: Measurement

    7. Measurement 9. Event log The relay continuously measures the phase currents and the To collect sequence-of-events information, the relay has a non- neutral current. Furthermore, the relay measures the phase volatile memory capable of storing 1024 events with the asso- voltages and the residual voltage.
  • Page 16: Condition Monitoring

    R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L Figure 8. Recording and event capabil- ities overview PROCESS LEVEL...
  • Page 17: Fuse Failure Supervision

    14. Fuse failure supervision The standard configuration D includes one conven- The relay includes fuse failure supervision function- tional residual current (Io 0.2/1 A) input and three ality. The fuse failure supervision detects failures sensor inputs for the direct connection of three between the voltage measurement circuit and the combi-sensors with RJ-45 connectors.
  • Page 18: Station Communication

    R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L — Table 4. Input/output overview Std.
  • Page 19 The IEC 61850 standard specifies network redundancy which In PRP, each network node is attached to two independent net- improves the system availability for the substation communi- works operated in parallel. The networks are completely sepa- cation. The network redundancy is based on two complemen- rated to ensure failure independence and can have different tary protocols defined in the IEC 62439-3 standard: PRP and topologies.
  • Page 20 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L HSR applies the PRP principle of parallel operation cost and complexity.
  • Page 21 Figure 11. Self-healing Ethernet ring solution Client A Client B Network A Network B Managed Ethernet switch Managed Ethernet switch with RSTP support with RSTP support All communication connectors, except for the front DNP serial and DNP TCP can be used in parallel. If port connector, are placed on integrated optional required, both IEC 61850 and DNP protocols can be communication modules.
  • Page 22 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L Required accuracy of grandmaster clock is +/-1 μs. The relay supports the following high accuracy time synchronization method with a time-stamping res- The relay can work as a master clock per BMC algo-...
  • Page 23: Technical Data

    19. Technical data — Table 6. Dimensions Description Value frame 177 mm Width case 164 mm frame 177 mm (4U) Height case 160 mm Depth case 201 mm (153 + 48mm) complete protection relay 4.1 kg Weight plug-in unit only 2.1 kg —...
  • Page 24 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L — Table 10. Binary inputs Description Value Operating range...
  • Page 25 — Table 14. Double-pole power output relays with TCS function Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s 30 A Breaking capacity when the control-circuit time constant L/R<40 ms, at 48/110/220 V DC (two contacts connected in series) 5 A/3 A/1 A Minimum contact load...
  • Page 26 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L — Table 19. IRIG-B Description Value IRIG time code format...
  • Page 27 Description Type test value Reference Radio frequency interference test 10 V (rms) IEC 61000-4-6 f = 150 kHz...80 MHz IEC 60255-26, class III 10 V/m (rms) IEC 61000-4-3 f = 80...2700 MHz IEC 60255-26, class III 10 V/m ENV 50204 f = 900 MHz IEC 60255-26, class III 20 V/m (rms)
  • Page 28 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L — Table 24. Insulation tests Description Type test value Reference...
  • Page 29 Protection functions — Table 30. Three-phase non-directional overcurrent protection (PHxPTOC) Characteristic Value Depending on the frequency of the measured current: fn ±2 Hz PHLPTOC ±1.5% of the set value or ±0.002 x I ±1.5% of set value or ±0.002 x I Operation accuracy PHHPTOC (at currents in the range of 0.1…10 x I...
  • Page 30 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L — Table 32. Non-directional earth-fault protection (EFxPTOC) Characteristic Value Depending on the frequency of the measured current: f...
  • Page 31 — Table 34. Directional earth-fault protection (DEFxPDEF) Characteristic Value Depending on the frequency of the measured current: f ±2 Hz Current: ±1.5% of set value or ±0.002 x I DEFLPDEF Voltage: ±1.5% of set value or ±0.002 x I Phase angle: ±2°...
  • Page 32 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L — Table 36. Three-phase undervoltage protection (PHPTUV) Characteristic Value Depending on the frequency of the measured current: f...
  • Page 33 — Table 40. Negative-sequence overvoltage protection (NSPTOV) Characteristic Value Depending on the frequency of the measured current: f Operation accuracy ±1.5% of the set value or ±0.002 × U Minimum Typical Maximum Start time (1), (2) = 1.1 x set Start value 33 ms 35 ms 37 ms...
  • Page 34 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L — Table 44. Negative-sequence overcurrent protection for machines (MNSPTOC) Characteristic Value Depending on the frequency of the measured current: f...
  • Page 35 — Table 48. Motor load jam protection (JAMPTOC) Characteristc Value Depending on the frequency of the measured current: f ±2 Hz Operation accuracy ±1.5% of the set value or ±0.002 × I Reset time Typically 40 ms Reset ratio Typically 0.96 Retardation time <35 ms Operate time accuracy in definite time mode...
  • Page 36 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L — Table 52. Phase reversal protection (PREVPTOC) Characteristic Value Depending on the frequency of the measured current: f...
  • Page 37 — Table 57. Circuit breaker failure protection (CCBRBRF) main settings Parameter Function Value (range) Step Current value CCBRBRF 0.05...2.00 × I 0.05 CCBRBRF Current value Res 0.05...2.00 × I 0.05 1 = Current CB failure mode CCBRBRF 2 = Breaker status 3 = Both —...
  • Page 38 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L Control functions —...
  • Page 39 Condition and supervision functions — Table 64. Circuit-breaker condition monitoring (SSCBR) Characteristic Value ±1.5% or ±0.002 × I (at currents in the range of 0.1…10 × I ±5.0% Current measuring accuracy (at currents in the range of 10…40 × I Operate time accuracy ±1.0% of the set value or ±20 ms Travelling time measurement...
  • Page 40 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L Measurement functions —...
  • Page 41 — Table 74. Sequence voltage measurement (VSMSQI) Characteristic Value Depending on the frequency of the voltage measured: fn ±2 Hz At voltages in range 0.01…1.15 × U Operation accuracy ±1.0% or ±0.002 × U Suppression of harmonics DFT: -50 dB at f = n × f , where n = 2, 3, 4, 5,…...
  • Page 42 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L Other functions —...
  • Page 43: Local Hmi

    20. Local HMI fault single line diagram. The SLD view can also be The relay is available with two optional displays, a accessed using the Web browser-based user inter- large one and a small one. The large display is face. The default SLD can be modified according to suited for relay installations where the front panel user requirements by using the Graphical Display user interface is frequently used and a single line di-...
  • Page 44: Mounting Methods

    CT secondary circuits when a relay unit is with- der Number Tool, supports order code creation for drawn from its case. The relay case is further pro- ABB Distribution Automation IEC products with vided with a mechanical coding system preventing emphasis on, but not exclusively for, the Relion the current measuring relay units from being in- product family.
  • Page 45: 24. Accessories And Ordering Data

    24. Accessories and ordering data — Table 82. Cables Item Order number Optical sensor for arc protection, cable length 1.5 m 1MRS120534-1.5 Optical sensor for arc protection, cable length 3.0 m 1MRS120534-3 Optical sensor for arc protection, cable length 5.0 m 1MRS120534-5 Optical sensor for arc protection, cable length 7.0 m 1MRS120534-7...
  • Page 46: Tools

    R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L 25. Tools abled via the local HMI.
  • Page 47: Cyber Security

    — Table 85. Tools Function Web HMI PCM600 Relay parameter setting • • Saving of relay parameter settings in the relay • • Signal monitoring • • Disturbance recorder handling • • Alarm LED viewing • • Access control management •...
  • Page 48: Terminal Diagrams

    R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L 27. Terminal diagrams —...
  • Page 49 — Figure 17. Terminal diagram of standard configuration B...
  • Page 50 R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L — Figure 18. Terminal diagram of standard configuration D...
  • Page 51: Certificates

    28. Certificates 29. References DNV GL has issued an IEC 61850 Edition 2 Certifi- ABB Substation Automation portal provides in- cate Level A1 for Relion® 615 series. Certificate formation on the entire range of distribution auto- number: 7410570I-OPE/INC 15-1136. DNV GL has is- mation products and services.
  • Page 52: Functions, Codes And Symbols

    R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L 30. Functions, codes and symbols —...
  • Page 53 — Table 86. Functions included in the relay (continued) Function IEC 61850 ANSI Measurement Disturbance recorder RDRE Load profile record LDPRLRC LOADPROF Fault record FLTRFRC FAULTREC Three-phase current measurement CMMXU IA, IB, IC Sequence current measurement CSMSQI I1, I2, I0 Residual current measurement RESCMMXU Three-phase voltage measurement...
  • Page 54: Document Revision History

    R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L 31. Document revision history —...
  • Page 56 — ABB Inc. 4300 Coral Ridge Drive Coral Springs, Florida 33065 Phone: +1 954 752 6700 abb.com/mediumvoltage abb.com/substationautomation © Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice.