5.2.1.3. fa07 (frequency reference from internal option)
Frequency reference is set up by 0.01Hz unit and the hexadecimal number.
For example, when "Frequency reference" is set up to 80Hz, since the minimum unit is 0.01Hz,
80 / 0.01 = 8000 = 0x1F40 (Hex.)
5.2.1.4. fa50 (Terminal output data from communication)
By setting up the data of the bit 0 - 1 of terminal output data (fa50) from communication, setting data
(OFF or ON) can be outputted to the output terminal.
Please select the functional number 92 - 95 as the selection (f130 - f138) of the output terminal
function before using it.
bit
Specified data output
0
(Output terminal No.: 92, 93)
Specified data
1
(Output terminal No.: 94, 95)
2-15
(Reserved)
Note: Set 0 to reserved bit
5.2.1.5. fa51 (Analog output (FM) data from communication)
Use this function, set the FM terminal meter selection parameter (fmsl) to 18 (communication data
output).
This makes it possible to send out the data specified as FM analog output data (fa51) though the FM
analog output terminal. Data can be adjusted in a range of 0 to 1000 (resolution of 10 bit).
Please refer to "Meter setting and adjustment" Section of the VF-MB1/S15 instruction manual for details.