 Do not install the unit stacked up, horizontally or upside down. Doing so will prevent proper
cooling of the unit and cause overheating inside.
 Do not install the unit above devices which generate heat such as heaters, transformers or
large scale resistors.
 In order to eliminate any effects from noise emission, power wires and electromagnetic
devices should be kept at least 100 mm away from the surfaces of the unit. When installing
the unit behind the doors of the control board, be especially careful to secure clearances as
above.
 Secure a clearance of at least 170 mm from the mounting surface of the PLC body for
connecting programming tools and cables.