Specifications

8.1 CPU Unit Specifications

8.1.1 General Specifications

Items
Rated voltage
Operating voltage range
Momentary power off time
Operating ambient
temperature
Storage ambient
temperature
Operating ambient humidity
Storage ambient humidity
Breakdown voltage
(Note 3)
Insulation resistance
(Note 4)
Vibration resistance
Shock resistance
Noise resistance
Environment
EU Directive applicable
standard
Overvoltage category
Pollution degree
(Note 1) When a programmable display GT series is connected to the GT power supply terminal of the CPU unit, use
it within the range of 21.6 to 26.4 V DC.
(Note 2) 10 ms when an AC power supply unit (AFP7PSA1/AFP7PAS2) is used
(Note 3) Cutoff current: 50 mA
(Note 4) With 500 V DC megohmmeter
8-2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
24V DC
20.4 to 28.8V DC (Note 1)
When the CPU unit only (DC) is used
4 ms (20.4 V is used) , 7 ms (24 V is used) , 10 ms (28.8 V is used)
(Note 2)
0 to +55C
-40 to +70C
10 to 95%RH (at 25C, no-condensing)
10 to 95%RH (at 25C, no-condensing)
All of the COM port, USB and LAN port
- All of the power supply terminals and functional earths
All of the COM port, USB and LAN port
- All of the power supply terminals and functional earths
Based on JIS B 3502 and IEC 61131-2:
5 to 8.4 Hz, half amplitude 3.5 mm
8.4 to 150 Hz, constant acceleration 9.8 m/s
X, Y and Z axes, 10 minutes, 10 sweeps (1 octave/mm)
Based on JIS B 3502 and IEC 61131-2
2
147 m/s
, X, Y and Z axes, 3 times
1,000 V[P-P] with pulse widths 50 ns and 1 µs (using a noise simulator) (power
supply terminals)
Free from corrosive gases and excessive dust.
EMC Directive: EN 61131-2, Low-Voltage Directive: EN 61131-2
Category II or lower
Pollution degree 2 or lower
Description
2
500V AC,
1 minute
100 M or
larger

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents