Rated Voltage; Cpu Unit Specifications; General Specifications - Panasonic FP7 Series User Manual

Cpu unit
Hide thumbs Also See for FP7 Series:
Table of Contents

Advertisement

8.1 CPU Unit Specifications

8.1 CPU Unit Specifications

8.1.1 General Specifications

General Specifications

Items

Rated voltage

Allowable voltage range
Allowable momentary
power drop duration
Allowable maximum
current
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient humidity
Breakdown voltage
Insulation resistance
Vibration resistance
Shock resistance
Noise resistance
Environment
EU Directive applicable
standard
Overvoltage category
Pollution degree
(Note 1)
When a programmable display GT series is connected to the GT power supply terminal (24 V) of the
CPU unit (CPS4R*/CPS3R*), use it within the range of 21.6 to 26.4 V DC.
(Note 2)
10 ms when an AC power supply unit (AFP7PSA1/AFP7PAS2) is used
(Note 3)
For details of the current consumption of a system, refer
Restrictions on Combination"
8-2
24 V DC
(Note 1)
20.4 to 28.8 V DC
When the CPU unit (DC) is used
4 ms (20.4 V is used), 7 ms (24 V is used), 10 ms (28.8 V is used)
(Note 2)
Max. 2.0 A at 0 to 55°C, Max. 3.0 A at 0 to 50°C
(Note 3)
0 to +55°C
-40 to +70°C
10 to 95%RH (at 25°C, no-condensing)
10 to 95%RH (at 25°C, no-condensing)
All of the expansion bus connectors - All of the power supply
terminals and functional earths
All of the COM port, USB and LAN port- All of the power supply
terminals and functional earths
All of the expansion bus connectors - All of the power supply
terminals and functional earths
Conforming to JIS B 3502 and IEC 61131-2
5 to 8.4 Hz, 3.5 mm single amplitude
8.4 to 150 Hz, constant acceleration of 9.8 m/s
10 sweeps each in X, Y and Z directions in 10 minutes (1 octave/mm)
Conforming to JIS B 3502 and IEC 61131-2
2
147 m/s
, three times each in the X, Y, Z directions
1,000 V[P-P] with pulse widths 50 ns and 1 µs (using a noise simulator) (power
supply terminals)
Free from corrosive gases and excessive dust.
EMC Directive: EN 61131-2, Low-Voltage Directive: EN 61131-2
Category II
Pollution degree 2
Description
(Note 3)
2
to"1.4 Selection of Power Supply and
500V AC,1
minute
100 M or larger
WUME-FP7CPUH-09

Advertisement

Table of Contents