The following parameters can effect on the correct operation of the protection:
cable length, i.e. the longer the cable the weaker the fuse protection, as the long cable limits the
fault current
cable size, i.e. the smaller the cable the weaker the fuse protection, as the small cable size limits the
fault current
transformer size, i.e the smaller the transformer the weaker the fuse protection, as the small
transformer limits the fault current
transformer impedance, i.e. the higher the z
limits the fault current.
The protection can be improved by installing a bigger supply transformer and/or bigger cables, and in
most cases by selecting aR fuses instead of gG fuses. Selection of smaller fuses improves the
protection, but may also affect the fuse life time and lead to unnecessary operation of the fuses.
In case of any uncertainty regarding the drive protection, please contact your local ABB.

Cable types

The table below gives copper and aluminium cable types for different load currents.
Cable sizing is based on max. 9 cables laid on a cable ladder side by side, ambient
temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and
IEC 60364-5-52/2001). For other conditions, size the cables according to local
safety regulations, appropriate input voltage and the load current of the drive.
Copper cables with concentric
Max. load current
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
copper shield
Cable type
2
A
mm
13
3×1.5
18
3×2.5
24
3×4
30
3×6
42
3×10
56
3×16
71
3×25
88
3×35
107
3×50
137
3×70
167
3×95
193
3×120
223
3×150
255
3×185
the weaker the fuse protection as high impedance
k
Aluminium cables with concentric
copper shield
Max. load current
Cable type
A
61
69
83
107
130
151
174
199
235
274
3 × (3×50)
260
2 × (3×95)
2
mm
3×25
3×35
3×50
3×70
3×95
3×120
3×150
3×185
3×240
3BFA 01051905 C
Technical data
101

Hide quick links: