Cable Types - ABB ACS800-U4 Hardware Manual

Drive modules
Hide thumbs Also See for ACS800-U4:
Table of Contents

Advertisement

106
ACS800-U4
Frame size
type
Three-phase supply voltage 525 V, 575 V, 600 V
-0011-7
R4
-0016-7
R4
-0020-7
R4
-0025-7
R4
-0030-7
R4
-0040-7
R4
-0050-7
R5
-0060-7
R5
-0070-7
R6
-0100-7
R6
-0120-7
R6
-0145-7
R6
-0175-7
R6
-0205-7
R6

Cable types

Cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or
earth (directly buried). For other conditions, dimension the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.
Max. load current
Technical data
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Input
current
A
A
10
20
13
20
19
30
21
30
29
45
32
45
45
70
51
80
70
100
82
125
103
150
121
200
150
200
188
250
Copper cables with concentric copper shield
A
18
22
31
44
57
75
88
101
114
132
154
176
202
224
251
Fuse
V
Manufacturer
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
Cable type
AWG/kcmil
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250 MCM or 2 x 1
300 MCM or 2 x 1/0
PDM code: 00096931
Type
UL class
JJS-20
T
JJS-20
T
JJS-30
T
JJS-30
T
JJS-45
T
JJS-45
T
JJS-70
T
JJS-80
T
JJS-100
T
JJS-125
T
JJS-150
T
JJS-200
T
JJS-200
T
JJS-250
T
PDM code: 00096931-J