Prevention of Unexpected Start, AGPS board

WARNING! Dangerous voltages can be present on the AGPS board even when the
115...230 V supply is switched off. Follow the
this manual and the instruction in this section when working on the AGPS board.
Make sure that the drive is disconnected from the mains (input power) and the
115...230 V source for the AGPS board is switched off during installation and
maintenance. If the drive is already connected to the mains, wait for 5 min after
disconnecting mains power.
Connect the optional AGPS board as follows:
• Remove the enclosure cover by undoing the fixing screws (1).
• Ground the unit via the bottom plate of the enclosure or via terminal X1:1 of the
AGPS board.
• Connect the cable delivered with the kit between terminal block X2 of the AGPS
board (2) and drive terminal block X41.
• Connect a cable between connector X1 of the AGPS board (3) and the
115...230 V source.
• Fasten the enclosure cover back with screws.
115...230 V
Electrical installation