2.3.1 CPE030/CRE030 and CPE040/CRE040

Serial Ports CPE030/CRE030 & CPE040/CRE040
Each CPU has three independent, on-board serial ports, accessed by connectors on
the front of the module. COM1 and COM2 provide serial interfaces to external
devices; either can be used for firmware upgrades. The third serial port is a dedicated
Ethernet Station Manager port. For serial port pin assignments, electrical isolation
and details on serial communications, refer to Chapter 5.
Ethernet Ports CPE030/CRE030 & CPE040/CRE040
Two RJ45 ports support Ethernet communications. Refer to RX7i Embedded
Ethernet Interface for details.
Indicators CPE030/CRE030 & CPE040/CRE040
Seven CPU LEDs indicate the operating status of various CPU functions.
Two Comm LEDs indicate activity on COM1 and COM2.
LED State
On
Blinking
CPU OK
On Green
Off
Blinking Green
Other LEDs off
CPU OK
Blinking in unison CPU is in boot mode and is waiting for a firmware
RUN
OUTS ENA
RUN
On Green
Off
OUTS ENA
On Green
Off
I/O FORCE
On Yellow
BATTERY
On Red
SYS FLT
On Red
C1 (COM1)
Blinking Green
C2 (COM2)
GFK-2222AD
CPU Operating State
Off
CPU has passed its power-up diagnostics and is
functioning properly.
CPU problem. RUN and OUTPUTS ENABLED LEDs
may be blinking in an error code pattern, which can
be used by technical support for diagnostics. This
condition and any error codes should be reported to
your technical support representative.
CPU in Stop/Halt state; possible watchdog timer
fault. Refer to the fault tables. If PME cannot
connect, cycle power with battery attached and
refer to fault tables.
update through a serial port.
CPU is in RUN Mode.
CPU is in STOP Mode.
Output scan is enabled.
Output scan is disabled.
Override is active on a bit reference
(Not used by CRE030 or CRE040.)
Battery has failed or is not attached.
CPU is in Stop/Faulted mode because a fatal fault
has occurred.