Chapter 2. CPU Features & Specifications
RDSD Indicators CPE302/CPE305 & CPE310
CPE302/
CPE310 LED
CPE305 LED
SYS FLT
RDSD / COM2
45
45
RDSD
RDSD
Ethernet Indicators CPE302/CPE305 & CPE310
LED
100
LINK
Error Checking and Correction
CPE302, CPE305 and CPE310 do not support error checking and correction (ECC).
45
RDSD active: RDSD attached to USB-A RDSD port.
74
LED State
On Red
Off or
Blinking
Green
/COM2
On Green
Blinking
Green
On Red
Blinking Red
Off
LED State
On Green
Off
On Amber
Blinking Amber
Off
PACSystems* RX7i, RX3i and RSTi-EP CPU Reference Manual
On
Blinking
RDSD Operating State
The RDSD has been removed during a store. The
CPU must be power cycled to resume RDSD
operations.
Valid RDSD connected or data transfer complete.
Data transfer in progress.
RDSD fault. Check for and correct the following
conditions:
CPU type mismatch with project on RDSD.
Data transfer error.
Corrupted or invalid USB file system.
Insufficient space on RDSD.
RDSD-Controller project name mismatch.
RDSD not attached or USB port is disabled.
On
Blinking
CPU Operating State
Network data speed is 100 Mbps.
Network data speed is 10 Mbps.
The link is physically connected.
Traffic is detected at the corresponding port.
No connection detected.