GE PACSystems RX7i Reference Manual page 130

Cpu
Hide thumbs Also See for PACSystems RX7i:
Table of Contents

Advertisement

Scan Parameters
Window Timer
(Available only when Sweep Mode is set to Constant Window.) The maximum combined
(ms)
execution time per scan for the Controller Communications Window, Backplane
Communications Window, and Background Communications Window. This value cannot
be greater than the value for the watchdog timer.
Valid range: 3 through 255, in increments of 1.
Default: 10.
Number of Last
(Available
Scans
The number of scans to execute after the PACSystems CPU receives an indication that a
transition from RUN Mode to STOP Mode should occur. (Used for STOP and STOP-Fault, but
not STOP-Halt.)
Choices: 0, 1, 2, 3, 4, 5.
Default:
GFK-2222AD
only
for
CPUs
0 when creating a new PACSystems target.
0 when converting a Series 90-70 target to a PACSystems target.
1 when converting a Series 90-30 target to a PACSystems target.
April 2018
Chapter 3. CPU Configuration
with
firmware
version
1.5
and
greater.)
119