Detection cycle
This function is executed in the cycle set by the count cycle change function.
Setting method
1.
Set "Warning output selection" to "Warning output function valid".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Application setting]  [Warning
output function]
2.
Set "Warning output setting value upper/upper limit", "Warning output setting value upper/lower limit", "Warning output
setting value lower/upper limit", and "Warning output setting value lower/lower limit" to values.
Item
Warning output setting value upper/upper limit
Warning output setting value upper/lower limit
Warning output setting value lower/upper limit
Warning output setting value lower/lower limit
Set values within the range satisfying the condition that upper/upper limit  upper/lower limit > lower/upper
limit  lower/lower limit.
1 FUNCTIONS
30
1.7 Warning Output Function
Setting range
0 to 32767