CH1 Warning output setting value lower/upper limit
Set the lower/upper limit value of the warning output function.
For details on the warning output function, refer to the following.
Page 29 Warning Output Function
■Buffer memory addresses
The following shows the buffer memory addresses of this area.
Buffer memory name
CH Warning output setting value lower/upper limit
CH Warning output setting value lower/upper limit
(when Q series-compatible mode is used)
■Setting range
• The setting range is from 0 to 32767.
• For channels on which the set value is outside the setting range, a warning output setting value lower/upper limit setting
error (error code: 1AC3H) occurs.
• Set the value so that the condition of upper/upper limit  upper/lower limit > lower/upper limit  lower/lower limit is satisfied.
If a value that does not meet this condition is set, a warning output setting value setting error (error code: 1AC5H) will occur.
However, the value can be set such that upper/upper limit = upper/lower limit and lower/upper limit = lower/lower limit.
• The default values of the upper/upper limit, upper/lower limit, lower/upper limit, and lower/lower limit are 0, so change each
warning output setting value when using the warning output function.
■Enabling the setting
Turn on and off 'Operating condition setting request flag' (Y1).
■Default value
The default value is 0 for all channels.
CH1 Warning output setting value lower/lower limit
Set the lower/lower limit value of the warning output function.
For details on the warning output function, refer to the following.
Page 29 Warning Output Function
■Buffer memory addresses
The following shows the buffer memory addresses of this area.
Buffer memory name
CH Warning output setting value lower/lower limit
CH Warning output setting value lower/lower limit
(when Q series-compatible mode is used)
■Setting range
• The setting range is from 0 to 32767.
• For channels on which the set value is outside the setting range, a warning output setting value lower/lower limit setting
error (error code: 1AC4H) occurs.
• Set the value so that the condition of upper/upper limit  upper/lower limit > lower/upper limit  lower/lower limit is satisfied.
If a value that does not meet this condition is set, a warning output setting value setting error (error code: 1AC5H) will occur.
However, the value can be set such that upper/upper limit = upper/lower limit and lower/upper limit = lower/lower limit.
• The default values of the upper/upper limit, upper/lower limit, lower/upper limit, and lower/lower limit are 0, so change each
warning output setting value when using the warning output function.
■Enabling the setting
Turn on and off 'Operating condition setting request flag' (Y1).
■Default value
The default value is 0 for all channels.
APPX
84
Appendix 3 Buffer Memory Areas
CH1
CH2
CH3
139
171
203
21
53
85
CH1
CH2
CH3
140
172
204
22
54
86
CH4
CH5
CH6
235
267
299
117
149
181
CH4
CH5
CH6
236
268
300
118
150
182
CH7
CH8
331
363
213
245
CH7
CH8
332
364
214
246