Condition target channel setting [n]
Set a channel where an interrupt is detected.
Setting value
0
1
2
3
4
5
6
7
8
An interrupt factor is monitored for according to 'Condition target setting [n]' (Un\G760 to Un\G775) in the channel set by this
area.
If a value other than the above is set, a condition target channel setting range error (error code: 182H) occurs.
"n" indicates an interrupt setting number. (n = 1 to 16)
■Buffer memory addresses
The following shows the buffer memory addresses of this area.
Buffer memory name
1
Condition target channel setting
760
[n]
Condition target channel setting
[n] (when Q series-compatible
mode is used)
■Enabling the setting
Turn on and off 'Operating condition setting request flag' (Y1).
■Default value
The default value is All channels (0) for all areas.
2
3
4
5
6
761
762
763
764
765
Setting details
All channels
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
7
8
9
10
11
766
767
768
769
770
Appendix 3 Buffer Memory Areas
12
13
14
15
16
771
772
773
774
775