Mitsubishi Electric MELSEC-Q series Programming Manual page 46

Qna programming manual (pid control instructions)
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

• Complete derivative
Setting
Data
Data Item
data
No.
Common
1
Number of
setting
loops
data
2
Number of
loops in one
scan
Data for
1
Selection of
each loop
operational
expression
2
Sampling
cycle (T
3
Proportional
constant (K
4
Integral
constant (T
5
Derivative
constant (T
6
Filter
coefficient ()
5 PID CONTROL PROCEDURE
44
5.1 PID Control Data
Description
Sets the number of loops
for which PID operation
will be executed.
Sets the number of loops
for which single PID
operation will be
executed when the
multiple loops reaches
the sampling cycle time.
Selects the PID
operational expression
indicated in Section
3.1.2/Section 3.2.2. (
Page 15 Operation
expressions,  Page
21 Operation
expressions)
Sets the cycle of PID
)
operation.
S
PID operation
)
proportional gain
P
This constant expresses
)
the magnitude of the
I
integral operation (I
operation) effect.
Increasing the integral
constant slows down the
manipulated value
change.
This constant expresses
)
the magnitude of the
D
derivative operation (D
operation) effect.
Increasing the derivative
constant causes a
significant change in the
manipulated value even
with slight change of the
control objective.
Sets the degree of
filtering applied to the
process value.
The filtering effect
decreases as the value
gets closer to 0.
Complete derivative
With PID limits
Setting
User
Range
Specification
Range
1 to 32
1 to 32
1 to 32
1 to 32
Forward
0 or 1
operation: 0
Reverse
operation: 1
0.01 to
1 to 6000
60.00s
(unit: 10 ms)
0.01 to
1 to 10000
100.00
(unit: 0.01)
0.1 to
1 to 32767
3000.0s
(unit: 100 ms)
Infinite()
(If the setting
for T
I
exceeds
3000.0 s)
0.00 to
0 to 30000
300.00s
(unit: 10 ms)
0 to 100%
0 to 100
Without PID limits
Setting
User
Range
Specification
Range
1 to 32
1 to 32
1 to 32
1 to 32
Forward
0 or 1
operation: 0
Reverse
operation: 1
0.01 to 60.00s
1 to 6000
(unit: 10 ms)
0.01 to 100.00
1 to 10000
(unit: 0.01)
0.1 to 3000.0s
1 to 32767
(unit: 100 ms)
Infinite()
(If the setting
for T
exceeds
I
3000.0 s)
0.00 to
0 to 30000
300.00s
(unit: 10 ms)
0 to 100%
0 to 100
Processing
when Set Data
is Outside the
Allowable
Setting Range
An error occurs
and PID operation
is not executed for
all loops.
An error occurs
and PID operation
for the
corresponding
loop is not
executed.
An error occurs
and PID operation
for the
corresponding
loop is not
executed.
An error occurs
and PID operation
for the
corresponding
loop is not
executed.