Application planning

5.2 Installation location

5.2
Installation location
Selection of the installation site / mounting position
You can install the PN/CAN LINK either in a control panel or on a standard mounting rail:
Permitted mounting positions and permitted ambient temperature
The table below show the permitted temperature range for the different mounting positions.
Mounting position
Horizontal
Vertical
Lying
Hanging
Ensure that condensation is not produced at a relative humidity between 10% and 95%.
Ensure that the atmospheric pressure is between 795 hPa and 1080 hPa. This corresponds
to an installation height of -1000 m to +2000 m.
The PN/CAN LINK is designed for natural heat dissipation through convection. Therefore
observe sufficient clearances:
● For horizontal mounting position: At least 35 mm above and below the PN/CAN LINK
● For vertical mounting position: At least 35 mm to the left and right of the PN/CAN LINK
58
Permitted ambient temperature
-25 ... +60 °C
-25 ... +55 °C
-25 ... +45 °C
-25 ... +45 °C
SIMATIC PN/CAN LINK
Operating Instructions, 03/2018, A5E39895388-AB