7.6
Connecting the CAN bus
CAN connection
CAN connection pin
assignment
NOTICE
The connection CAN Ground to ground is necessary to ensure EMC stability.
The common return (CAN_GND) may only be connected in one place to the ground
potential in the CAN network.
NOTICE
EMC stability is only guaranteed with shielded CAN cables.
SIMATIC PN/CAN LINK
Operating Instructions, 03/2018, A5E39895388-AB
The PN/CAN LINK is connected to the CAN bus by
means of a CAN cable with D-sub connector (9-pin,
socket)
CiA specifications with shielded connector for the
connection.
1
--
2
CAN_L
3
CAN_GND
4
--
5
CAN_SHLD
6
CAN_GND
7
CAN_H
8
--
9
--
7.6 Connecting the CAN bus
①
. Use a shielded CAN cable conforming to
Terminating resistor 120 Ω
(install jumper from pin 1 to pin 2 for use)
CAN_L bus cable (dominant low)
CAN Ground
Not connected
CAN shield
CAN Ground
CAN_H bus cable (dominant high)
Not connected
Not connected
Connecting
71