Siemens 6RA70 Series Instructions Manual page 104

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

Fault
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Armature current peaks are too small at α=30° and EMF=0
3
(armature current peak value <50% of I A, motor or <50% of I A,rated )
Possible cause:
Armature circuit inductance is too high (field supply from armature terminals)
P150 (Alpha G limit) has been set to excessively high value
Possible remedy:
Reduce P100 (I A,motor ) while this optimization run is in progress
4
The armature circuit inductance (P111) cannot be determined from the sampled values of the armature current and line
voltage of the armature current crest last generated
Possible cause:
•P100 (I A,motor ) or r072.i002 (I A,rated ) very much smaller than actual motor rated current of the armature
•L A >327.67mH (armature circuit inductance too large)
•P100 (I A,motor ) very much smaller than r072.i002 (I A,rated )
•Armature circuit short-circuited
5
Offset adjustment of actual field current sensing is not possible
(value detected for P825 is outside permissible value range)
Possible cause:
Fault in actual field current sensing circuit
(defective A7004 gating board or A7001 electronics board)
7
The field circuit resistance (P112) is indeterminable
(the actual field current does not reach the internally specified setpoint of 95% of P102 as a result of P112 variation)
Possible cause:
R A >3276.7Ω
Fault in actual field current sensing circuit (defective gating board or A7001 electronics board)
The command "Inject standstill field" is applied
P102 is set too high
A thyristor in the field bridge is not firing
8
80% of rated EMF (K287=P101 – P100 * P110) cannot be reached within 15s (or maximum of the three set acceleration
times)
Possible cause:
Acceleration time (P303, P307, P311) is set too low
P101 does not match the set maximum speed (U A at n max < P101) or setting for P102 is too low
The command "Ramp-function generator enable"=0 or "Ramp-function generator stop"=1
9
Field current control loop is not stable enough to record field characteristics
(30s after injection of internal field current setpoint, actual field current is deviating by more than (0.39% of P102 + 0.15 %
of r073.002) from the setpoint)
Possible cause:
Field current controller or field current precontrol is not optimized or optimized badly (check P112, P253 to P256 or
execute a current controller optimization run (P051=25))
10
Field characteristic is not uniform
(i.e. in spite of field current setpoint reduction, the flux values of this measuring point calculated from EMF and actual speed
are rising)
Possible cause:
High armature reaction and sharp load variations during recording of field characteristics
Field current controller or field current precontrol is not optimized or optimized badly (check P112, P253 to P256 or
execute a current controller optimization run (P051=25))
A lower field current limit of ≥ 50% of P102 (I F,motor ) is applied
11
(for this reason, it is not possible to plot a minimum of 9 field weakening measuring points)
Possible cause:
P103 ≥ 50% of P102
Check P614 !
Siemens Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
Description
Further information (r047.002 to r047.016)
9-15

Advertisement

Table of Contents
loading

Table of Contents