P140 Selection Of Pulse Encoder Type; P141 Number Of Pulses Of Pulse Encoder; P142 Matching To Pulse Encoder Signal Voltage - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

PNU
Description
Notes on selecting a pulse encoder (number of pulses):
The lowest speed which can be measured by a pulse encoder is calculated with the following equation:
=
n
[
rev
/
min]
21973
min
X
The following applies:
X = 1 for 1x evaluation of pulse encoder signals (P144=0)
2 for 2x evaluation of pulse encoder signals (P144=1)
4 for 4x evaluation of pulse encoder signals (P144=2)
see also "Single/multiple evaluation of encoder pulses"
Lower speeds are interpreted as n=0.
The frequency of the pulse encoder signals at terminals 28 and 29 or 30 and 31 must not be higher than 300 kHz.
The highest speed which can be measured by a pulse encoder is calculated with the following equation:
18000000
=
n
[
rev
/
min]
max
P
141
When selecting a pulse encoder, therefore, it is important to ensure that the lowest possible speed ≠ 0 is significantly higher than n
the highest possible speed does not exceed n
21973
>>
IM
X
n
[
rev
/
min]
min
18000000
IM
n
[
rev
/
min]
max
Single/multiple evaluation of encoder pulses:
The setting for single/multiple evaluation of encoder pulses is applicable for both the speed and position sensing functions.
1x evaluation:
Only the rising edges of one pulse track are evaluated (applies to all encoder types).
2x evaluation:
The rising and falling edges of one pulse track are evaluated (can be set for encoder types 1, 1a and 2).
4x evaluation:
The rising and falling edges of both pulse tracks are evaluated (can be set for encoder types 1 and 1a)
See parameters P450 and P451 for position sensing function
P140
Selection of pulse encoder type
See beginning of this Section (11.8) for pulse encoder types
(G145)
0
No encoder/"Speed sensing with pulse encoder" function not
selected
1
Pulse encoder type 1
2
Pulse encoder type 1a
3
Pulse encoder type 2
4
Pulse encoder type 3
P141
Number of pulses of pulse encoder
(G145)
P142
Matching to pulse encoder signal voltage
0
Pulse encoder outputs 5 V signals
(G145)
1
Pulse encoder outputs 15V signals
Matching of internal operating points to signal voltage of incoming pulse
encoder signals.
CAUTION
Resetting parameter P142 to the alternative setting does not switch
over the supply voltage for the pulse encoder (terminals X173.26 and
27). Terminal X173.26 always supplies +15V. An external voltage
supply is must be provided for pulse encoders requiring a 5V supply.
10-28
1
Formula applies with a nominal measuring time of 1 ms when P146=0 and P147=0
P
141
.
max
Equations for selection of pulses per revolution IM of pulse encoder
Value range
[Unit]
Steps
0 to 4
1
1 to 32767
[pulses/rev]
1 pulse/rev
0 to 1
1
SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
and
min
Ind: None
P052 = 3
FS=0
P051 = 40
Type: O2
Offline
Ind: None
P052 = 3
FS=500
P051 = 40
Type: O2
Offline
Ind: None
P052 = 3
FS=1
P051 = 40
Type: O2
Offline