Interface Error; F008 Line Frequency Less Than The Minimum Line Frequency Acc. To Parameter P363 (Active In Operating States Of ≤ 05); F009 Line Frequency Greater Than The Maximum Line Frequency Acc. To Parameter P364 (Active In Operating States Of ≤ 05); F011 Telegram Failure At Gsst1 - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

Fault
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
NOTICE
This monitoring function is deactivated in the delivery state. It can be activated via parameter P820.
Fault value:
1
Overvoltage has occurred
4
Undervoltage persists for longer than time set in
parameter P086 (if this is >0)
F008
Line frequency less than the minimum line frequency acc. to parameter P363
(active in operating states of ≤ o5)
This fault message is activated if the line frequency is less than the minimum line frequency (for longer than the "restart time" set
in parameter P086).
Note: Up to software version 1.7 the threshold for activation of the fault message (minimum line frequency) is 45Hz.
Fault value:
1
Frequency of the armature supply < minimum line frequency
2
Frequency of the field supply < minimum line frequency
4
Line frequency less than the minimum line frequency for longer than set in parameter P086 (if >0)
F009
Line frequency greater than the maximum line frequency acc. to parameter P364
(active in operating states of ≤ o5)
This fault message is activated if the line frequency is greater than the maximum line frequency (for longer than the "restart time"
set in parameter P086).
Note: Up to software version 1.7 the threshold for activation of the fault message (maximum line frequency) is 65Hz
Fault value:
1
Frequency of the armature supply > maximum line frequency
2
Frequency of the field supply > maximum line frequency
4
Line frequency greater than the maximum line frequency for longer than set in parameter P086 (if >0)
9.1.2.2

Interface error

F011
Telegram failure at GSST1
when P780 = 2:
USS telegram failure at G-SST1
(active from the first receipt of a valid protocol in all operating states)
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter P787.
Possible fault causes
♦ Cable break
♦ Error in USS master
Siemens Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
Description
Further information (r047.002 to r047.016)
r047 Index 002 to 016:
002 Number of phase that has activated fault message
0.... Phase UV
1.... Phase VW
2.... Phase WU
3.... Phase field
i003 Incorrect voltage value (normalized to 16384)
-
9-5