Panasonic GT Series Manual page 55

Connection with other companies’ plcs
Hide thumbs Also See for GT Series:
Table of Contents

Advertisement

For almost all models the PLC communication setting method is as follows. However, differences
may arise depending on the model. For details, please consult the manual for the PLC you will
use when making the settings.
To communicate using the RS232C port of the CPU unit
Set the system area as follows.
Address
Value set
DM6600
0201 (HEX)
DM6645
0001 (HEX)
DM6646
0004 (HEX)
DM6648
0000 (HEX)
To communicate using the communication port
Set the system area as follows.
To communicate with port A
Address
Value set
DM6600
0201 (HEX)
DM6550
0001 (HEX)
DM6551
0004 (HEX)
To communicate with port B
Address
Value set
DM6600
0201 (HEX)
DM6555
0001 (HEX)
DM6556
0004 (HEX)
To communicate using the high link I/F unit
Make sure set the CPU mode to monitor mode.
Use the DIP switch or rotary switch on the link I/F unit to make settings such as the baud rate.
For details please refer to the manual for the unit you are using.
To communicate using the peripheral port
Set the system area as follows.
Address
Value set
DM6600
0201 (HEX)
DM6550
0001 (HEX)
DM6551
0004 (HEX)
Setting of PLC main unit mode (monitor mode)
Mode setting of RS232C port (high link)
Setting of communication conditions (19200 bps, 7 bits, even, 1 bit)
Setting of device number (Device No. 0)
Setting of PLC main unit mode (monitor mode)
Mode setting of RS232C port (high link)
Setting of communication conditions (19200 bps, 7 bits, even, 1 bit)
Setting of PLC main unit mode (monitor mode)
Mode setting of RS232C port (high link)
Setting of communication conditions (19200 bps, 7 bits, even, 1 bit)
Setting of PLC main unit mode (monitor mode)
Mode setting of RS232C port (high link)
Setting of communication conditions (19200 bps, 7 bits, even, 1 bit)
Setting
Setting
Setting
Setting
2-17