Installing I/O Modules - Siemens SIMATIC S7-1500 Automation System System Manual

Hide thumbs Also See for SIMATIC S7-1500 Automation System:
Table of Contents

Advertisement

5.6

Installing I/O modules

Introduction
The I/O modules are installed following the CPU. I/O modules form the interface between the
controller and the process. The controller detects the current process state via the connected
sensors and actuators, and triggers the corresponding reactions.
Requirements
The following preconditions have to be fulfilled to mount an I/O module:
● The mounting rail is installed.
● The CPU is installed.
● In the module / CPU located on the left next to the I/O module, a U-connector is inserted
Tools required
Screwdriver with 4.5 mm blade
Installing I/O modules
Proceed as follows to install an I/O module:
1. Insert a U-connector into the back right on the I/O module.
2. Install the I/O module on the mounting rail and slide the I/O module up to module on the
3. Pivot the I/O module towards the back.
4. Fasten the I/O module (torque 1.5 Nm).
S7-1500 Automation System
System Manual, 01/2013, A5E03461182-01
on the back right.
Exception: the last I/O module in the assembly.
left.
Figure 5-7
Installing I/O module
Installation
5.6 Installing I/O modules
51