11.38 Current-Balance Supervision
11.38
Current-Balance Supervision
Setting Values
Release threshold
Threshold min/max
Delay failure indication
Dropout Ratio
Overcurrent dropout ratio
Undercurrent dropout ratio
Times
Tripping time
Dropout time
1206
I
= 1 A
rated
I
= 5 A
rated
0.030 A to 35.000 A
0.15 A to 175.00 A
0.10 to 0.95
0.00 s to 100.00 s
Approx. 0.97
Approx. 1.05
Approx. 500 ms
Approx. 500 ms
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018
Increments of 0.001 A
Increments of 0.01 A
Increments of 0.01
Increments of 0.01 s