Siemens SIPROTEC 5 Technical Data Manual page 112

High-voltage bay controller, v7.80 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

11.39
Voltage-Balance Supervision
Setting Values
Release threshold
Threshold min/max
Delay failure indication
Dropout Ratio
Overvoltage dropout ratio
Undervoltage dropout ratio
Times
Tripping time
Dropout time
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018
0.300 V to 170.000 V
0.58 to 0.95
0.00 s to 100.00 s
Technical Data
11.39 Voltage-Balance Supervision
Increments of 0.001 V
Increments of 0.01
Increments of 0.01 s
Approx. 0.97
Approx. 1.05
Approx. 500 ms
Approx. 500 ms
1207