Instantaneous High-Current Tripping - Siemens SIPROTEC 5 Technical Data Manual

High-voltage bay controller, v7.80 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Technical Data

11.13 Instantaneous High-Current Tripping

11.13
Instantaneous High-Current Tripping
Setting Values
Threshold value
Dropout ratio
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer
Instrument current transformer
Times
Operate time for current > 2·√2·threshold value
Tolerances
Response tolerance, current
Time delays
65
OOT (Output Operating Time) Additional delay of the output medium used, see Chap.
1160
1 A @ 100 Irated
5 A @ 100 Irated
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
0.030 A to 35.000 A
0.15 A to 175.00 A
0.030 A to 35.000 A
0.15 A to 175.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.50 to 0.90
15 mA sec. (I
= 1 A) or
rated
75 mA sec. (I
= 5 A)
rated
0.5 mA sec. (I
= 1 A) or
rated
2.5 mA sec. (I
= 5 A)
rated
Approx. 8 ms + OOT
65
5 % of setting value or 10 mA
at I
= 1 A
rated
5 % of setting value or 50 mA
at I
= 5 A
rated
1 % of the setting value or 10 ms
11.1.4 Relay Outputs
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018
Increments of 0.001 A
Increments of 0.01 A
Increments of 0.001 A
Increments of 0.01 A
Increments of 0.001 A
Increments of 0.001 A
Increments of 0.01