11.46 Measuring-Voltage Failure Detection
11.46
Measuring-Voltage Failure Detection
Setting Values
3ph.fail. - VA,VB,VC <
3ph.fail. - phs.curr.release 1 A @ 50 and 100 Irated
3ph.fail. - phs.curr. jump
Asym.fail. - time delay
SO 3ph.fail. - time delay
Dropout
The larger dropout differential (= | pickup value – dropout threshold |) of the following 2 criteria
is used:
Dropout differential derived from the Dropout ratio parameter
If this parameter is not available, a dropout ratio of 95 % applies to the overvoltage protection and a dropout
ratio of 105 % applies to the undervoltage protection.
Minimum absolute dropout differential
Times
Pickup time
Dropout time
Times
Use in function group Line
Pickup time
Use in other function group types
Pickup time
Frequency Operating Range
0.9 ≤ f/f
≤ 1.1
rated
10 Hz ≤ f < 0.9 f
1.1 f
< f ≤ 80 Hz
rated
94
OOT (Output Operating Time) Additional delay of the output medium used, see chapter
95
OOT (Output Operating Time) Additional delay of the output medium used, for example 5 ms with fast relays, see chapter
Outputs
96
OOT (Output Operating Time) Additional delay of the output medium used, for example 5 ms with fast relays, see chapter
Outputs
1214
5 A @ 50 and 100 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
1 A @ 50 and 100 Irated
5 A @ 50 and 100 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
rated
0.300 V to 340 000 V
0.030 A to 35.000 A
0.15 A to 175.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 35.000 A
0.15 A to 175.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.00 s to 30.00 s
0.00 s to 30.00 s
150 mV sec.
Approx. 10 ms + OOT
94
at 50 Hz
Approx. 10 ms + OOT at 60 Hz
Approx. 20 ms + OOT
Approx. 10 ms + OOT
95
at 50 Hz
Approx. 9 ms + OOT at 60 Hz
Approx. 20 ms + OOT
96
at 50 Hz
Approx. 18 ms + OOT at 60 Hz
According to specified tolerances
Slightly expanded tolerances
11.1.4 Relay Outputs
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018
Increments of 0.001 V
Increments of 0.001 A
Increments of 0.01 A
Increments of 0.001 A
Increments of 0.001 A
Increments of 0.001 A
Increments of 0.01 A
Increments of 0.001 A
Increments of 0.001 A
Increments of 0.01 s
Increments of 0.01 s
11.1.4 Relay