Controlling the safety functions
5.6 Control via TM54F
5.6
Control via TM54F
The activation via TM54F is described in detail in the SINAMICS S120 Safety Integrated
Function Manual.
The "SINAMICS S120 Safety Integrated Function Manual" is available on the Internet at the
following address (https://support.industry.siemens.com/cs/ww/en/ps/13231/man).
5.6.1
Control via TM54F for SINAMICS G130, S120 Chassis
The TM54F Terminal Module must be supplied with 24 VDC and connected to the Control
Unit via DRIVE-CLiQ.
Fire hazard due to overheating because of inadequate ventilation clearances
Insufficient ventilation clearances result in overheating with danger to persons as a result of
smoke and fire. This can also result in more downtimes and reduced service lives of the
Terminal Module.
• For this reason, it is imperative that you maintain the 50 mm clearances above and
5.6.2
Control via option K87 for SINAMICS S120 Cabinet Modules
With option K87 the Terminal Module TM54F is integrated in the cabinet unit (-A70) and
connected with the Control Unit via DRIVE-CLiQ.
5.6.3
Control via K87 for SINAMICS S150
With option K87 the Terminal Module TM54F is integrated in the cabinet unit (-A70) and
connected with the Control Unit via DRIVE-CLiQ.
96
WARNING
below the Terminal Module.
Safety Integrated
Function Manual, 07/2016, A5E03264275A