Key Points Of Installation - ABB ESP M1R Installation Instructions Manual

Mains protectors
Table of Contents

Advertisement

1.

Key points of installation

1.1 Install protectors very close to the power supply to be
protected, either within the distribution panel or directly
alongside it.
1.2 Mount units within a panel or WBX enclosure.
1.3 Units are installed in parallel.
1.4 Connect to phases, neutral and earth.
NOTE: Units must have a neutral connection (see 3.4).
1.5 Units installed at power distribution boards can be
installed either:
– on the load side of the incoming isolator, or
– on the closest available outgoing way to the incoming
supply
1.6 Provide a means of isolation for the ESP unit.
1.7 The connecting leads to phase/live terminals should be
suitably fused (125 A maximum) ensuring full
discrimination with the immediate upstream supply fuse.
Installation instructions for mains wire-in protectors | 1/1