ABB DNP31.0 Technical Description page 18

Devicenet interface
Table of Contents

Advertisement

Connection Object, Instance 4 = COS/Cyclic I/O Message Connection, Attributes
Attribute
Access
Name
1
Get
State
2
Get
Instance Type
3
Get
Transport Class Trigger
4
Get
Produced Connection ID
5
Get
Consumed Connection ID
6
Get
Initial Comm. Characteristics
7
Get
Produced Connection Size
8
Get
Consumed Connection Size
9
Get/Set
Expected Packet Rate
12 (0x0C)
Get
Watchdog Timeout Action
13 (0x0D)
Get
Produced Conn. Path Length
14 (0x0E)
Get
Produced Connection Path
15 (0x0F)
Get
Consumed Conn. Path Length
16 (0x10)
Get
Consumed Connection Path
17 (0x11)
Get/Set
Production Inhibit Time
*1) Connection state
0
nonexistent
1
configuring
2
wait for connection ID
3
established
4
timed out
5
deferred
*2) xxxxxx = node address
*3) The size of Produced and Consumed Connection depends on the device connected to the DNP31 (as
of writing UMC100.3). For detailed information, please refer to the device manual.
*4) Transport Class Trigger
0x00
Cyclic, unacknowledged
0x02
Cyclic, acknowledged
0x10
COS, unacknowledged
0x12
COS, acknowledged
Common Services
Service Code
Class
05 (0x05)
No
14 (0x0E)
No
16 (0x10)
No
DNP31.0 Data sheet
Instance
Service Name
Yes
Reset
Yes
Get_Attribute_Single
Yes
Set_Attribute_Single
Type
Value
USINT
*1)
1 = I/O Connection
USINT
BYTE
*4)
UINT
01101xxxxxx
UINT
10xxxxxx101
BYTE
0x01 (acknowledged)
0x0F (unacknowledged)
UINT
*3)
UINT
*3)
UINT
in ms
USINT
0 = time out
UINT
6
EPATH
20 04 24 64 30 03
UINT
6
EPATH
20 04 24 65 30 03
UINT
in ms
- 18 -
*2)
*2)
Issue: 09.2015

Advertisement

Table of Contents
loading

Table of Contents