8.6.3.3

Line/load connection

Table 8- 15
Line/load connection of the Active Line Module
Terminals
U1, V1, W1
3 AC power input
DCP, DCN
DC power output
PE connection
Dimensions for connecting alternative cable lugs, see "Cable lugs" in the Appendix.
1)
8.6.3.4

X9 terminal strip

Table 8- 16
Terminal strip X9
Terminal
1
1
2
2
3
4
5
6
7
8
Max. connectable cross-section 1.5 mm
Note
Connection to terminals 7 and 8
For operation, 24 V DC must be connected to terminal 7 and ground to terminal 8. Pulse
suppression is activated when removed.
Grid infeed
System Manual, 04/2015, A5E03347436A
8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format
Technical data
Voltage:
3 AC 500 V -10 % (-15 % < 1 min) ... 3 AC 690 V +10 %
Frequency: 47 ... 63 Hz
Connecting lugs:
Frame size HXL: d = 13 mm (M12/50 Nm) for cable lugs in accordance with DIN 46234 / DIN
46235
1)
Frame size JXL: d = 13 mm (M12/50 Nm) for busbar connection
Voltage:
750 ... 1035 V DC
Connecting lugs: d = 13 mm (M12/50 Nm) for busbar connection
Connecting lugs:
Frame size HXL: d = 13 mm (M12/50 Nm) for cable lugs in accordance with DIN 46234 / DIN
46235
1)
Frame size JXL: d = 13 mm (M12/50 Nm) for busbar connection
Signal name
P24 V
P24 V
M
M
Bypass contactor control
Pre-charge contactor control
EP +24 V (Enable Pulses)
EP M1 (Enable Pulses)
2
Technical data
Voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption: See Technical data
for Active Interface Module, -X609;11
for Active Interface Module,-X609;12
for Active Interface Module, -X609;9
for Active Interface Module, -X609;10
Supply voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption: 10 mA
Device overview