NOTICE
Risk of motor overheating for incorrectly connected KTY temperature sensor
A KTY temperature sensor connected with incorrect polarity cannot detect if the motor
overheats.
• Make sure that you connect the KTY temperature sensor with the correct polarity.
Note
The temperature sensor connection can be used for motors that are equipped with a KTY84-
1C130 or PTC probe in the stator windings.
Note
Connection to terminal strip -X9
A cable harness is used to connect terminals -X41:1 and -X41:2 to terminals -X9:8 and -
X9:7.
8.6.3.6

X42 terminal strip

Table 8- 18
Terminal strip X42 voltage supply for Control Unit, Sensor Module and Terminal Module
Terminal
1
2
3
4
Max. connectable cross-section 2.5 mm
Note
Connection options of terminal strip X42
The terminal strip is not intended to supply other 24 VDC loads (for example, for supplying
other components on the plant/system side), as the voltage supply of the Control Interface
Module could also be overloaded and result in malfunctions.
Grid infeed
System Manual, 04/2015, A5E03347436A
8.6 Liquid-cooled Active Line Modules for the grid infeed, chassis format
Function
P24L
M
2
Technical data
Power supply for Control Unit, Sensor Module and Ter-
minal Module (18 ... 28.8 V)
maximum load current: 3 A
Device overview
177