7.4 Commissioning example for an infeed with voltage and frequency control for an island grid.
7.4.7
Signal interfaces
Description
The following signals are required by the drive unit for operation and/or provided for
monitoring purposes.
Signals transferred to the drive unit
This involves a list of typical signals for communication with the higher-level control system.
Table 7- 6
Signals transferred to the drive unit
Parameter
Drive Object
p0840[0]
INFEED
p5401
INFEED
p3611
INFEED
p5406[0...1]
INFEED
p5416[0...1]
INFEED
p5451
INFEED
Grid infeed
System Manual, 04/2015, A5E03347436A
Signal
BI: ON/OFF1
Sets the signal source for control word 1 bit 0
(ON/OFF1).
BI: Grid control activation
1 signal: Activation of grid droop control and
deactivation of closed-loop DC-link voltage con-
trol/closed-loop current control.
0 signal: Activation of grid droop control and
deactivation of closed-loop DC-link voltage con-
trol/closed-loop current control.
CI: Infeed reactive current supplementary set-
point
Reactive current setpoint for operation with
p5401 = 0
CI: Grid droop control frequency droop supple-
mentary setpoint
dynamic supplementary frequency setpoint for
operation with p5401 = 1
CI: Grid droop control voltage droop supplemen-
tary setpoint
dynamic supplementary voltage setpoint for
operation with p5401 = 1
BI: Current hysteresis controller operating mode
Parallel operation with diesel generator
1 signal: Combined operation
(INFEED and additional infeeds together supply
the island grid, INFEED is not the power generat-
ing unit with the highest short-circuit power)
0 signal: Operation by itself
(INFEED exclusively supplies the island grid
and/or is the power generating unit with the
highest short-circuit power)
Commissioning
Type
Unit
Bit
-
Bit
-
Unsigned32 /
-
FloatingPoint32
Unsigned32 /
-
FloatingPoint32
Unsigned32 /
-
FloatingPoint32
Bit
-
83