10 Safety instructions
WARNING!
General warning warns about maintenance work on the roof which should always
be done from the outer perimeter, considering the local safety regulations.

Allowed usage

The PVS-100/120 medium voltage compact skid (MVCS) is designed to transform AC
current from a group of inverters and finally feed to a medium voltage grid. Use the
MVCS only at its permissible input/output ratings and ambient conditions. Make sure
this compliance is satisfied before commissioning.
The operation and maintenance of the MVCS must be carried out by certified technicians
that fulfill all local skill set and safety requirements. Any unqualified personnel must
maintain a safe distance from the MVCS. All activities must be in accordance with the
criteria described in the ABB technical documents and local regulations.
Make changes to the MVCS only with the direct authorization of ABB. Any alterations
done outside ABB approval will invalid the warranty for the product. ABB is not liable
for any damages caused by these changes.
The MVCS is a non-walk-in type station, designed to be operated from the outside.
Make sure the side doors are closed at all times during operation and that no personnel
is inside or in the near vicinity of the MVCS.

Safe installation, start-up and maintenance

This section contains the safety instructions which you must follow when installing,
commissioning and maintaining the MVCS. If ignored, physical injury or death may follow,
or damage may occur to the equipment.
Only authorized electricians are allowed to install, start-up and maintain the MVCS.
Working methods, tools, components etc. must follow the IEC regulations.
Obey all local safety regulations concerning electrical stations.
The MVCS should be energized and de-energized only by an authorized person who
has the task-specific instructions for the operation of an MV substation and permission
from the on-site foreperson in charge of electrical work.
If other people must be in the vicinity while the door is open, warn them, and if required,
provide supervision and guidance.

General safety instructions

WARNING!
Before you perform any work in the MVCS, obey the following safety precautions.
1. Clearly identify the work location.
2. Read the safety instructions of the work area and the component you are working on.
See the subsections below and the component-specific manuals.
3. Disconnect and secure against reconnection.
4. Disconnect all possible power supplies (external, auxiliary and inverters) and open all
base fuse switches. Lock the disconnectors in the open position and attach a warning
notice to them. After disconnecting power to the inverters, always wait until the stored
energy of the inverters is discharged. See also, inverters manual.
5. Use protection against any live parts.