● Motor Module additional data / Power Module additional data
Allows filter settings for modules of the "VECTOR" type drive object.
The procedure for detail settings is identical for Motor Modules and Power Modules.
Procedure
Detailed settings are shown below, using a Power Module as an example.
1. Select the desired Power Module in the device view and open the Inspector window.
2. Select the menu "Power Module Details > Power Module Settings" in the Inspector
window.
The preallocated supply voltage is displayed in the screen forms:
Figure 5-18
3. Enter a new supply voltage as required.
4. If you use the "VECTOR" drive object type, you can set additional data.
Select the menu "Power Module Details > Power Module Additional Data" in the Inspector
window.
5. Select a desired filter in the "Output filter" drop-down list.
Getting Started, 12/2018, 6SL3097-5AG30-0BP0
Example: Power Module Settings
NOTICE
Damage to a sine-wave filter through incorrect parameter assignment
If a sine-wave filter is installed in your hardware configuration, the sine-wave filter can
be destroyed if it has not been set in the additional data of the Motor Module or Power
Module.
• Set the installed sine-wave filter in the "Output filter" drop-down list and add the
required filter parameter data.
5.4 Creating a project offline in Startdrive
Commissioning
83