Quick start-up 21

Connection procedure

1. Strip the input power cable. Ground the bare shield of the cable (if any) 360 degrees
under the grounding clamp. Fasten the grounding conductor (PE) of the input power
cable under the screw of the grounding clamp. Connect the phase conductors to the
U1, V1 and W1 terminals.
2. Strip the motor cable. Ground the bare shield of the cable 360 degrees under the
grounding clamp. Twist the shield to form as short a pigtail as possible and fasten it
under the screw of the grounding clamp. Connect the phase conductors to the U2, V2
and W2 terminals.
3. Connect DC input to the BRK+ and BRK- terminals with a shielded cable using the
same procedure as for the motor cable.
4. Secure the cables outside the drive mechanically.
Frame size
Tightening torque
R0...R2
R3
R4
To identify the frame size of your inverter, see
Max. wire size
N·m (lbf·in)
4.0/6.0 mm
0.8 (7)
10.0/16.0 mm
1.7 (15)
25.0/35.0 mm
2.5 (22)
2
(10 AWG)
2
(6 AWG)
2
(2 AWG)
Operating
instructions, page 24.