ABB ACS355 Manual page 57

Solar pump inverter (+n827)
Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

All parameters
No.
Name/
Value
DI3
DI4
DI5
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
WITH_P60.16
6016
MIN LOAD
CURRENT
0...2 * Drive
rating A
6017
DRY RUN TRP
TIME
0...5 mins
6018
DRY RUN RST
TIME
2...300 mins
6019
FAULT RESET
TIME
2...20 mins
Description
See selection DI1.
See selection DI1.
See selection DI1.
Inverted digital input DI1. Defines the inverted digital
input DI1 as the control for dry run protection.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See parameter
6016 MIN LOAD CURRENT
Defines the minimum load current for dry run
protection of inverter. When actual motor current is
less than this value for the time defined in 6017 DRY
RUN TRP TIME, the inverter trips due to
Current
Allows inverter to wait for this time to trip if pump is in
dry run condition. See 6016 MIN LOAD CURRENT.
Time
Allows inverter to wait for this time to reset in case of a
dry run fault. After this reset time, inverter starts
automatically.
Time
Allows inverter to wait for this time to restart
automatically in case inverter tripped due to under-
voltage fault, PV cell maximum voltage fault or when
actual speed decreased below the minimum motor
speed defined in
6006 PUMP MINIMUM
Time
Actual signals and parameters 57
DRY
RUN.
SPD.
Def/ FbEq
3
4
5
6
7
8
9
10
11
1 = 1 A
0
1 = 1 min
2 mins
1 = 1 min
2 mins
1 = 1 min
2 mins